| 2014-01-18 12:37:54 | PLUMBING PLAN REVIEW |
| | PERMIT: 13100124 |
| | ADD: 815 UPLAND RD |
| | CONT: MASTER PLAN INC |
| | TEL: (561) 683-9972 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SATURDAY JAN. 17/ 2014 |
| | ACTION: DENIED |
| | |
| | 2010 EXISTING BUILDING CODE |
| | METHOD OF COMPLIANCE: DESIGNER OF RECORD HAS CHOSEN |
| | PRESCRIPTIVE |
| | PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE BUILT IN |
| | 1930 |
| | |
| | 2010 FL EXST BLDG CODE 301.2.1 EXISTING MATERIALS. |
| | MATERIALS ALREADY IN USE IN A BUILDING IN COMPLIANCE |
| | WITH REQUIREMENTS OR APPROVALS IN EFFECT AT THE TIME OF |
| | THEIR ERECTION OR INSTALLATION SHALL BE PERMITTED TO |
| | REMAIN IN USE UNLESS DETERMINED BY THE CODE OFFICIAL TO |
| | BE DANGEROUS TO LIFE, HEALTH OR SAFETY. WHERE SUCH |
| | CONDITIONS ARE DETERMINED TO BE DANGEROUS TO LIFE, |
| | HEALTH OR SAFETY, THEY SHALL BE MITIGATED OR MADE SAFE. |
| | THE DEMOLITION PLANS SHOW THE LOCATION OF THE PLUMBING |
| | FIXTURES, WHEN THEY ARE MOVED IT NO LONGER IS EXISTING |
| | BUT CONSIDERED NEW WORK AND NEEDS TO COMPLY WITH THE |
| | 2010 FBC-PLUMBING. |
| | |
| | 2010 FL EXST BLDG CODE 301.2.2 NEW AND REPLACEMENT |
| | MATERIALS. |
| | EXCEPT AS OTHERWISE REQUIRED OR PERMITTED BY THIS CODE, |
| | MATERIALS PERMITTED BY THE APPLICABLE CODE FOR NEW |
| | CONSTRUCTION SHALL BE USED. LIKE MATERIALS SHALL BE |
| | PERMITTED FOR REPAIRS AND ALTERATIONS, PROVIDED NO |
| | HAZARD TO LIFE, HEALTH OR PROPERTY IS CREATED. |
| | HAZARDOUS MATERIALS SHALL NOT BE USED WHERE THE CODE |
| | FOR NEW CONSTRUCTION WOULD NOT PERMIT THEIR USE IN |
| | BUILDINGS OF SIMILAR OCCUPANCY, PURPOSE AND LOCATION. |
| | |
| | 1) 2ND REQUEST, PLEASE PROVIDE THE LOCATION OF THE |
| | WATER HEATER THE ELECTRICAL PLANS INDICATE THE USE OF |
| | INGIT OR WATER HEATER, LOCATION, SIZE, GAS OR ELECTRIC? |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010: |
| | 107.3.5.1.3 PLUMBING , |
| | (1) MINIMUM PLUMBING FACILITIES |
| | (2) FIXTURE REQUIREMENTS |
| | (5) WATER HEATERS |
| | |
| | 2) SHEET P-5 SHOWS THEAUTOMATIC CLOTHES WASHER WASTE |
| | BEING PUMPED INTO THE BUILDING DRAIN BY USE OF A SUMP |
| | PUMP. THERE ARE TWO ISSUES: |
| | 2A) PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION FOR |
| | THIS SUMP PUMP FOR SIZE AND FLOW RATE CAPACITY AS WELL |
| | AS THE CLOTHES WASHER PUMP DISCHARGE FLOW RATE TO |
| | VERIFY THE SIZING OF THE SUMP PUMP WILL HAVE ENOUGH |
| | CAPACITY TO ACCEPT THE DISCHARGE. P 712.3.1 SUMP PUMP |
| | CAPACITY AND HEAD SHALL BE APPROPRIATE TO ANTIIPATE USE |
| | REQUIREMENTS. |
| | |
| | 2B) SHEET P-5 NOTE ON THIS SHEET " SUMP PUMP TO CONNECT |
| | TO THE EXISTING SANITARY LINE, CONTRACTOR TO VERIFY THE |
| | SIZE & LOCATION AT SITE. THERE ARE STRICT REQUIREMENTS |
| | FOR THE TIEING INTO THE BUILDING SEWER OR BUILDING |
| | DRAIN. 2010 FBC-P 712.3.5 EJECTOR CONNECTION TO THE |
| | DRAINAGE SYSTEM. |
| | PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO |
| | THE BUILDING SEWER OR SHALL CONNECT TO A WYE FITTING IN |
| | THE BUILDING DRAIN A MINIMUM OF 10 FEET (3048 MM) FROM |
| | THE BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE |
| | DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO |
| | HORIZONTAL DRAINAGE PIPING, THE CONNECTOR SHALL BE MADE |
| | THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE |
| | PIPING. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |