2014-01-29 17:46:42THE FOLLOWING ITEMS SHALL BE ADDRESSED AND CORRECTED
 ACCORDINGLY:
 1. NOW THAT THE METHOD OF HEATING THE WATER HAS BEEN
 CLARIFIED, THE PRESSURIZATION AND DRAIN PUMP LOADS AND
 CIRCUITS SHALL BE INCLUDED IN PANEL H.
 2. HAVING THE COMMUNAL LAUNDRY FACILITIES IN THE
 BASEMENT BRING UP ADDITIONAL REQUIREMENTS FOR PROPER
 LIGHTING OF BOTH THE LAUNDRY ROOM AND THE STAIRS TO THE
 BASEMENT. THAT CIRCUIT HAS TO BE INCLUDED IN TO PANEL H
 AS WELL.
 3. THE FBC-ENERGY CONSERVATION CODE HAS SPECIFIC
 LIGHTING REQUIREMENTS, NOT OF WHICH ALL HAVE BEEN
 ADDRESSED. INCLUDE A LIGHTING DIAGRAM/SCHEMATIC
 INDICATING HOW THE HOUSE LIGHTS WILL BE CONTROLLED.
 INCLUDE THE ENTRY TO THE BASEMENT. IF THE BASEMENTS
 STAIR LIGHTING IS NOT ON AUTOMATIC SENSING, A MANUAL
 SWITCH SHALL BE PROVIDED PRIOR TO ENTERING THE STAIRS.
 4. PANEL H DOES NOT INCLUDE THE REQUIRED DEDICATED
 CIRCUIT FOR THE FIRE ALARM CONTROL PANEL, (FCP).
 5. BOTH THE FBC AND THE NFPA REQUIRE THAT THE FIRE
 ALARM CONTROL PANEL (FCP) BE PROTECTED WITH A SMOKE
 DETECTOR.
 6. ADDITIONAL FIRE ALARM RELATED COMMENTS MATCH THOSE
 ALREADY ADDRESSED BY THE FIRE REVIEW.
  