| 2014-01-16 16:55:10 | BUILDING PLAN REVIEW |
| | PERMIT: 13100124 |
| | ADD: 815 UPLAND RD |
| | CONT: MASTER PLAN INC |
| | TEL: (561) 683-9972 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURSDAY JAN. 16/ 2014 |
| | ACTION: BUILDING PROVISO |
| | |
| | 2010 EXISTING BUILDING CODE |
| | METHOD OF COMPLIANCE: DESIGNER OF RECORD HAS CHOSEN |
| | PRESCRIPTIVE |
| | PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE BUILT IN |
| | 1930 |
| | |
| | 2010 FL EXST BLDG CODE 301.2.1 EXISTING MATERIALS. |
| | MATERIALS ALREADY IN USE IN A BUILDING IN COMPLIANCE |
| | WITH REQUIREMENTS OR APPROVALS IN EFFECT AT THE TIME OF |
| | THEIR ERECTION OR INSTALLATION SHALL BE PERMITTED TO |
| | REMAIN IN USE UNLESS DETERMINED BY THE CODE OFFICIAL TO |
| | BE DANGEROUS TO LIFE, HEALTH OR SAFETY. WHERE SUCH |
| | CONDITIONS ARE DETERMINED TO BE DANGEROUS TO LIFE, |
| | HEALTH OR SAFETY, THEY SHALL BE MITIGATED OR MADE SAFE. |
| | |
| | 1929 BUILDING CODE CITY OF WEST PALM BEACH |
| | FIRE SEPERATION SEC 1300 H - OCCUPANCY HOTEL, |
| | APARTMENTS, ROOMING HOUSES & RESTARAUNTS (BETWEEN |
| | OCCUPANCIES) |
| | CHAP. XIII REQUIREMENTS FOR GROUP "H" OCCUPANCY ( SS) |
| | NOTE: SPECIAL SEPERATION |
| | TYPE V BUILD 2 STORY FRONTAGE ON ONE STREET 3600 SQ FT, |
| | CODE COMPLIANT, |
| | PARTIII DETAILED REGULATIONS CHAPTER 33 STAIRS AND |
| | EXITS (PAGE 87) THE NUMBER OF STAIRWAYS AND OR EXITS |
| | REQUIRED IN ANY BUILDING CLASSED IN GROUPS D,E,F,G AND |
| | I SHALL BE DETERMINED AS FOLLOW: |
| | NO REQUIREMENTS FOR TYPE H OCCUPANCY : HOTEL, |
| | APARTMENTS, ROOMING HOUSES & RESTARAUNTS FOR STAIRS OR |
| | EXITS IN REGARDS TO FIRE RATING. |
| | SECTION 3303. MINIMUM WIDTH OF STAIRS IS 34 INCHES IN |
| | GROUP- D,E,F,& G BUILDINGS. NO MIN FOR H OCCUPANCIES. |
| | CHAPTER 44 FIRE RESISTANCE STANDARDS, PROTECTION OF |
| | STRUCTURAL PARTS WOOD JOIST WITH FLOOR WITH DOUBLE |
| | BOARD ON TOP OF JOIST AND GYPSUM OR PORTLAND CEMENT |
| | PLASTER 3/4 HR |
| | IN THE 2010 FBC-B THE PRESCRIPTIVE FIRE RESISTANCE |
| | TABLE 720.1(3)13.1.1 THE SAME FLOOR CONFIGURATION WILL |
| | PROVIDE 7/8 HR PROTECTION. |
| | |
| | 1) 2010 FL EXST BLDG CODE 301.2.2 NEW AND REPLACEMENT |
| | MATERIALS. |
| | EXCEPT AS OTHERWISE REQUIRED OR PERMITTED BY THIS CODE, |
| | MATERIALS PERMITTED BY THE APPLICABLE CODE FOR NEW |
| | CONSTRUCTION SHALL BE USED. LIKE MATERIALS SHALL BE |
| | PERMITTED FOR REPAIRS AND ALTERATIONS, PROVIDED NO |
| | HAZARD TO LIFE, HEALTH OR PROPERTY IS CREATED. |
| | HAZARDOUS MATERIALS SHALL NOT BE USED WHERE THE CODE |
| | FOR NEW CONSTRUCTION WOULD NOT PERMIT THEIR USE IN |
| | BUILDINGS OF SIMILAR OCCUPANCY, PURPOSE AND LOCATION. |
| | |
| | 1A) THE WINDOW AND DOOR OPENINGS (THE INFILL) THAT ARE |
| | BEING CLOSED IN WILL NEED TO COMPLY WITH THE 2010 FL |
| | BLDG CODE REQUIRING A 1 HR FIRE RATING PER SECTION |
| | 709.1 GENERAL. |
| | THE FOLLOWING WALL ASSEMBLIES SHALL COMPLY WITH THIS |
| | SECTION. 1. WALLS SEPARATING DWELLING UNITS IN THE SAME |
| | BUILDING AS REQUIRED BY SECTION 438.2. 439.2 SEPARATION |
| | WALLS. |
| | WALLS SEPARATING DWELLING UNITS IN THE SAME BUILDING, |
| | WALLS SEPARATING SLEEPING UNITS IN THE SAME BUILDING |
| | AND WALLS SEPARATING DWELLING OR SLEEPING UNITS FROM |
| | OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME |
| | BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN |
| | ACCORDANCE WITH SECTION 709. 709.3 FIRE-RESISTANCE |
| | RATING. |
| | FIRE PARTITIONS SHALL HAVE A FIRE-RESISTANCE RATING OF |
| | NOT LESS THAN 1 HOUR. PROVIDE UL |
| | |
| | 1B) ANY NEW PENETRATION OF THE TENANT SEPERATION WALL |
| | OR FLOOR/ CEILING ASSEMBLY WILL ALSO REQUIRE COMPLIANCE |
| | WITH 713.3.1.2 THROUGH -PENETRATION FIRE STOP SYSTEMS. |
| | |
| | 1C) ALL NEW TENANT ENTRY DOORS ARE TO BE 1 HOUR FIRE |
| | RATED AS PER 2010 FBC-B TABLE 715.4 AND AS REQUESTED BY |
| | THE DESIGNER OF RECORD. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | THIS REVIEW WILL CONTINUE 01/17/2014 |
| | |
| | |