| Plan Review Notes For Permit 13100124 |
| Permit Number |
13100124 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-11-12 11:34:23 | THE INTENT OF THE FOLLOWING LLIST IS NOT TO CREATE A | | | "PUNCH :IST" FOR THE DESIGNER, NEVER THE LESS, THE | | | BELOW MENTIONED ITEMS AMONG OTHERS SHALL BE ADDRESSED: | | | 1. FBC-R 303.8 REQUIRES THAT HEATING BE PROVIDED, NON | | | OF WHICH IS REFLECTED ON EITHER THE ELECTRICAL PANEL | | | SCHEDULE, ELECTRICAL LOAD CALCS, OR ON THE AIR | | | CONDITIONING PAGE. | | | 2. THE PLANS DO NOT INDICATE IF THE WATER WILL BE | | | HEATED WITH GAS OR ELECTRIC, THEREFORE THE ELECTRICAL | | | LOAD CALC MAY NOT BE CORRECT. | | | 3. THE LEVEL OF ALTERATION DICTATES THE REQUIREMENT FOR | | | HAVING TO PROVIDE LAUNDRY FACILITIES, BUT THE NEC DOES | | | REQUIRE A LAUNDRY CKT BE INCLUDES IN THE LOAD CALCS. | | | 4. NEC 2008 SECTION 406.11 REQUIRE TAMPER-RESISTANT | | | DEVICES | | | 5. NEC 2008 SECTION 210.12 REQUIRES ARC-FAULT | | | PROTECTION | | | 6. THE SUBMITTED DRAWINGS SHOW THE AHU INSIDE AN | | | ATTIC/CEILING, THIS WILL REQUIRE COMPLIANCE W/NEC | | | 110.33(B) | | | 7. FBC-R SECTIONS 314 & 315 HAVE SPECIFIC SMOKE AND | | | CARBON MONOXIDE DETECTION REQUIREMENTS WHICH SHALL BE | | | ADHERED TO. | | | | | | SENT TO SH DESK | | | |
|