2013-11-12 11:34:23THE INTENT OF THE FOLLOWING LLIST IS NOT TO CREATE A
 "PUNCH :IST" FOR THE DESIGNER, NEVER THE LESS, THE
 BELOW MENTIONED ITEMS AMONG OTHERS SHALL BE ADDRESSED:
 1. FBC-R 303.8 REQUIRES THAT HEATING BE PROVIDED, NON
 OF WHICH IS REFLECTED ON EITHER THE ELECTRICAL PANEL
 SCHEDULE, ELECTRICAL LOAD CALCS, OR ON THE AIR
 CONDITIONING PAGE.
 2. THE PLANS DO NOT INDICATE IF THE WATER WILL BE
 HEATED WITH GAS OR ELECTRIC, THEREFORE THE ELECTRICAL
 LOAD CALC MAY NOT BE CORRECT.
 3. THE LEVEL OF ALTERATION DICTATES THE REQUIREMENT FOR
 HAVING TO PROVIDE LAUNDRY FACILITIES, BUT THE NEC DOES
 REQUIRE A LAUNDRY CKT BE INCLUDES IN THE LOAD CALCS.
 4. NEC 2008 SECTION 406.11 REQUIRE TAMPER-RESISTANT
 DEVICES
 5. NEC 2008 SECTION 210.12 REQUIRES ARC-FAULT
 PROTECTION
 6. THE SUBMITTED DRAWINGS SHOW THE AHU INSIDE AN
 ATTIC/CEILING, THIS WILL REQUIRE COMPLIANCE W/NEC
 110.33(B)
 7. FBC-R SECTIONS 314 & 315 HAVE SPECIFIC SMOKE AND
 CARBON MONOXIDE DETECTION REQUIREMENTS WHICH SHALL BE
 ADHERED TO.
  
 SENT TO SH DESK
  