| 2013-10-28 11:21:58 | BUILDING PLAN REVIEW |
| | PERMIT: 13100124 |
| | ADD: 815 UPLAND RD |
| | CONT: MASTER PLAN INC |
| | TEL: (561) 683-9972 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. OCT 28/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 2010 FL EXISSTING BUILDING CODE, THE DESIGNER OF |
| | RECORD HAS NOT COMPLIED WITH 2010 FL EXT DLDG CODE |
| | 101.5 COMPLIANCE METHODS. |
| | THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION |
| | OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1 |
| | THROUGH 101.5.3 AS SELECTED BY THE APPLICANT. |
| | APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR |
| | ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A |
| | SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE |
| | OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE |
| | APPLIED IN COMBINATION WITH EACH OTHER. |
| | |
| | 3) 107.3.5.1.1. MINIMUM PLAN REVIEW CRITERIA FOR |
| | COMMERCIAL BUILDINGS: |
| | OCCUPANCY TYPE ; R2 TRANSIENT OR NON-TRANSIENT |
| | BUILDING TYPE; |
| | FIRE SPRINKLERS: |
| | FIRE SEPERATION: TENANT WALLS & FLOOR CEILING |
| | ASSEMBLIES |
| | FIRE RATED DOORS; |
| | EXTERIOR STAIRS & REQUIREMENTS FOR FIRE RATED WINDOWS |
| | AND OR DOORS WITH-IN 10'-0" OF THE DOOR 2010 FBC-B |
| | 1026.6 |
| | EGRESS WINDOWS |
| | |
| | 3) THE DESIGNER OF RECORD DID NOT INCLUDE A EXISTING |
| | FLOOR PLAN, WITHOUT A EXISTING FLOOR PLANS AND |
| | KNOWLEDGE OF COMPLIANCE METHOD A BUILDING PLAN REVIEW |
| | IS JUST GUESS WORK!!!!! |
| | THE INFORMATION ABOVE WILL HELP DEFINE WHAT WE ARE |
| | ACTUALLY LOOKING FOR FOR MINIMUM PLAN REVIEW, WHAT IS |
| | ACTUALLY THERE FOR FIRE RESISTANCE RATINGS AND WHAT WE |
| | CAN ASK FOR UNDER THE EXISTING BUILDING CODE. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |