| 2013-10-22 14:33:52 | BUILDING PLAN REVIEW |
| | PERMIT: 131000123 |
| | ADD: 1779 PALM BEACH LAKES BLVD # W111 |
| | CONT: TO BE DETERMINED |
| | TEL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: OCT. 22/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET G-1 INDICATES AND OCCUPANT LOAD OF 109 WHICH |
| | REQUIRES 2 MEANS OF EGRESS (2010 FBC-B TABLE 1015.1), |
| | A1 & A-5 BOTH INDICATE THE USEAGE OF THE STOCKROOM AS |
| | THE SECOND MEANS OF EGRESS PLEASE PROVIDE CODE |
| | COMPLIANCE FOR: |
| | 1014.2 EGRESS THROUGH INTERVENING SPACES. |
| | 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| | ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| | EXCEPTIONS: |
| | 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| | FOLLOWING ARE MET: |
| | |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | |
| | 2.2 NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| | TO THE EXIT WITHOUT OBSTRUCTIONS |
| | |
| | .3) PB OUTLET MALLS: A LETTER FROM THE QUALIFIER OF |
| | BOTH THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT |
| | BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT |
| | BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | |