| Plan Review Notes For Permit 13100086 |
| Permit Number |
13100086 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-03 07:30:31 | BUILDING PLAN REVIEW | | | PERMIT: 13100086 | | | ADD: 1707 OKEECHOBEE RD | | | CONT: TO BE DETERMINED | | | TEL: (561) | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: OCT. 03/ 2013 | | | ACTION: DENIED | | | | | | 1) SHEET A1: | | | 1A) PLANS INDICATE A MIXED USE OCCUPANCY BUILDING, | | | WAREHOUSE AND MERCANTILE. PLEASE PROVIDE IF THE | | | WAREHOUSE IS S1 OR S2 STORAGE PLEASE REVIEW | | | 2010 FBC-B TABLE 508.4 DEPENDING ON THE TYPE OF | | | OCCUPANCY THE HOUR RATING REQUIRED FOR THIS WALL. | | | | | | 1B) SHEET A1 ALSO INDICATES THE INSULATION LAYING | | | DIRECTLY ON THE CEILING GRID. 2010 FBC-ENERGY 502.2.1.2 | | | CEILING INSULATION. | | | INSULATION INSTALLED ON A SUSPENDED CEILING WITH | | | REMOVABLE CEILING TILES SHALL NOT BE CONSIDERED PART OF | | | THE MINIMUM THERMAL RESISTANCE OF THE ROOF INSULATION | | | UNLESS THE ROOF/CEILING CAVITY IS SEALED FROM THE | | | EXTERIOR ENVIRONMENT. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|