2013-10-11 14:29:49PERMIT # 13100071
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-3 INDICATES LOCATION OF FIRE ALARM PULL
 STATION. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR
 THE INSTALLATION OR MODIFICATION OF THE FIRE ALARM
 SYSTEM.
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  