| 2013-10-28 16:16:14 | BUILDING PLAN REVIEW |
| | PERMIT: 13100069 |
| | ADD: 1801 N FLAGLER DR SUITE # 436 |
| | CONT: REGIONS PROPERTY MGMT & CONSTRUCTION, INC |
| | TEL: (561)292-9881 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY OCT 28/2013 |
| | ACTION: DENIED |
| | |
| | 1) IT APPEARS THERE MAY BE A DISCREPANCY IN THE PLANS |
| | AND PERMIT APPLICATION. THE PERMIT APPLICATION, WITH |
| | THE PCN NUMBER 74-43-43-15-39-001-4360 TIES THE WORK TO |
| | UNIT 436, ON THE FOURTH FLOOR AND WITHIN THE ACTUAL |
| | UNIT. THE PLANS APPEAR TO BE CREATING A NEW STORAGE |
| | AREA THAT IS NOT TIED TO THE FOUTH FLOOR SUITE 436. |
| | WITH CONDOMINIUMS WORK THAT IS TO BE COMPLETED WITHIN |
| | THE COMMON AREAS USE THE TRUNKATED PCN 74-43-43-15-39. |
| | PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF THIS |
| | NEW STORAGE ROOM, WHAT FLOOR IT IS TO BE LOCATED ON, IF |
| | IT FACES THE EXTERIOR, IF THE BACK WALL IS NEW OR IS |
| | THE FRONT WALL THE ONLY NEW EXTERIOR WALL. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. THIS IS |
| | CREATING NEW STORAGE ROOM, PLEASE PROVIDE COMPLIANCE |
| | WITH: 2010 FBC-B SECTION |
| | 2.1) 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 2.2) 1207.2.1 MASONRY. |
| | THE SOUND TRANSMISSION CLASS OF CONCRETE MASONRY AND |
| | CLAY MASONRY ASSEMBLIES SHALL BE CALCULATED IN |
| | ACCORDANCE WITH TMS 0302 OR DETERMINED THROUGH TESTING |
| | IN ACCORDANCE WITH ASTM E 90. |
| | |
| | 2.3) 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3) THE PLANS DO NOT INDICATE IF THE EXTERIOR DOORS ARE |
| | GOING TO REQUIRE A FIRE RESISTANCE RATING, IS THE |
| | BUILDING FIRE SPRINKLERED? |
| | |
| | 4) THE HEIGHT OF THE BUILDING IS ALSO NOT INDICATED, |
| | POSITIVE PRESSURES BUILD FROM GRADE, THE NEGATIVE |
| | PRESSURES ARE TAKEN FROM THE HEIGHT OF THE BUILDING |
| | PLEASE UPDATE PRESSURES, ALSO THE PLANS INDICATE A "C" |
| | EXPOSURE, THIS LOCATION IS NEXT TO THE INTERCOASTAL |
| | WATER WAY, IS CONSIDERED A "D" EXPOSURE PLEASE UPDATE |
| | PRESSURES. |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |