Plan Review Notes
Plan Review Notes For Permit 13100060
Permit Number 13100060
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-16 10:20:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS FOR WINDOWS TO BE
 REPLACED.
  
 FOR BEDROOM WINDOWS ONLY - NOTE EXISTING CONDITIONS
 (TYPE OF WINDOW) AND OPENING SIZE FOR BEDROOMS (OPENING
 WHICH EXISTS WITH WINDOW IN OPEN POSITION), FBC R310,
 FBC EB 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY
 MORE THAN 5%.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
 3. THE STOP WORK VIOLATION ISSUED INCLUDES FRAMING, BUT
 NO DETAILS WERE PROVIDED. THIS PERMIT WILL BE ISSUED
 WITH PROVISO THAT, SUBJECT TO FIELD INSPECTOR'S
 DISCRETION, AN ENGINEERED DETAIL MAY BE REQUIRED TO BE
 SUBMITTED AS A REVISION (WITH FEES). ALTERNATIVELY, A
 STRUCTURAL DETAIL MAY BE PROVIDED AT THIS TIME (NO
 FEE). FBC 2010 RESIDENTIAL 301.1.
  
 4. PERMIT APPLICATION IS LACKING INFORMATION - OWNER'S
 ADDRESS, OWNER'S NOTARIZED SIGNATURE, OWNER BUILDER
 AFFIDAVIT. PLEASE SUBMIT. FS489.
  
  
  
  
  
  
  
  