| Notes |
| Date |
Text |
| 2013-10-16 10:20:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS FOR WINDOWS TO BE | | | REPLACED. | | | | | | FOR BEDROOM WINDOWS ONLY - NOTE EXISTING CONDITIONS | | | (TYPE OF WINDOW) AND OPENING SIZE FOR BEDROOMS (OPENING | | | WHICH EXISTS WITH WINDOW IN OPEN POSITION), FBC R310, | | | FBC EB 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY | | | MORE THAN 5%. | | | | | | 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM | | | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) | | | | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4, | | | PROVIDE CALCULATIONS. | | | | | | 3. THE STOP WORK VIOLATION ISSUED INCLUDES FRAMING, BUT | | | NO DETAILS WERE PROVIDED. THIS PERMIT WILL BE ISSUED | | | WITH PROVISO THAT, SUBJECT TO FIELD INSPECTOR'S | | | DISCRETION, AN ENGINEERED DETAIL MAY BE REQUIRED TO BE | | | SUBMITTED AS A REVISION (WITH FEES). ALTERNATIVELY, A | | | STRUCTURAL DETAIL MAY BE PROVIDED AT THIS TIME (NO | | | FEE). FBC 2010 RESIDENTIAL 301.1. | | | | | | 4. PERMIT APPLICATION IS LACKING INFORMATION - OWNER'S | | | ADDRESS, OWNER'S NOTARIZED SIGNATURE, OWNER BUILDER | | | AFFIDAVIT. PLEASE SUBMIT. FS489. | | | | | | | | | | | | | | | | | | | | | | | | |
|