Plan Review Notes
Plan Review Notes For Permit 13090969
Permit Number 13090969
Review Stop B
Sequence Number 2
Notes
Date Text
2013-12-05 07:17:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. OK.
  
 3. REVISE PLAN TO SHOW OCCUPANCY CLASSIFICATION AND
 OCCUPANT LOAD FOR THE EXISTING BUILDING AND EXTERIOR
 COURTYARD. IT APPEARS THAT THE COURTYARD AREA IS
 CURRENTLY USED AS STORAGE AND WILL NOW BE A2. 1300
 SF/15 IS AN OCCUPANT LOAD OF 87 FOR THE COURTYARD.
 OCCUPANT LOAD OF EXISTING RESTAURANT NOT SHOWN AND
 CANNOT BE DETERMINED AS KITCHEN/BATHROOM/WAITING AREAS
 NOT SHOWN.
  
 PROVIDE A LIFE SAFETY PLAN, FBC CHAPTER 10. EXITING
 STRATEGY NOT CLEAR. A DOOR IS SHOWN AS "EMERGENCY
 EGRESS," EXIT SIGNS SHOWN, BUT EXITING PATH NOT SHOWN.
 SEE ALSO FBC 1008.1.2 AND 1008.1.10. INCLUDE ELEVATION
 CHANGES, IF ANY, WHICH EXIST THROUGHOUT THE PROPOSED
 MEANS OF EGRESS PATH.
  
 2ND REVIEW -
  
 DOOR STILL REFERENCED AS "EMERGENCY EGRESS." PLEASE
 ADVISE AS TO WHERE THE DEFINITION OF "EMERGENCY EGRESS"
 IS LOCATED IN FBC CHAPTER 10. IT IS NOT CLEAR WHAT
 FUNCTION THIS SERVES IN THE LIFE SAFETY PLAN. FBC 107.
  
 COURTYARD IS SHOWN AS "EXISTING OCCUPANCY" WITH 50 MAX.
 BASED ON THE PHOTOGRAPH ON THE PLAN AS WELL AS AERIALS,
 THIS ISS STORAGE, NOW PROPOSED AS A2, SO HOW CAN THIS
 BE "EXISTING OCCUPANCY"? OCCUPANT LOAD CANNOT BE LESS
 THAN FBC TABLE 1004.1.1.
  
 PLAN NOTES THAT THE COURTYARD IS OPEN TO THE PARKING
 LOT, WITH NO FENCE OR WALL, BUT AERIALS AND THE
 PHOTOGRAPH ON THE PLAN SHOW A FENCE, SO PLAN IS NOT
 CONSISTENT WITH JOB CONDITIONS. SHOW FENCE ON THE PLAN,
 AND INDICATE WHETHER THIS WILL BE REMOVED OR REMAIN.
 NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO DETERMINE
 REQUIREMENTS FOR THIS AREA.
  
 ELEVATION CHANGES NOT SHOWN.
  
 4. PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD
 REQUIRED, FAC9N-3, FBC 107 (DOOR). INDICATE HARDWARE
 AND THRESHOLD OPTIONS, SEE FBC 1008.1, FBC 1008.1.10
 AND FBC 2010 ACCESSIBILITY 404.
  
 2ND REVIEW, NOT ADDRESSED. ARCHITECT'S RESPONSE IS THAT
 PRODUCT APPROVAL IS ATTACHED.
  
 PANIC DEVICE REQUIRED, BUT NOT FOUND IN THE PRODUCT
 APPROVAL. SEE FBC 1008.1.10 AND FBC 1008.1. THRESHOLD
 NOT INDICATED, SEE FBC 2010 ACCESSIBILITY 404.
  
 5. PROVIDE A DETAIL FOR THE PROPOSED GATE. CODE
 REFERENCE AND REQUIREMENTS CANNOT BE PROVIDED AT THIS
 TIME, SEE ITEM 3. IF THERE ARE NO CODE REQUIREMENTS FOR
 THE GATE, THIS MAY NOT BE REQUIRED.
  
 NOT ADDRESSED. PHOTOGRAPH APPEARS TO SHOW A METAL
 SCREEN WITH MULTIPLE HINGES (3 PANELS). THE PHOTOGRAPH
 STATES "DECORATIVE ONLY - NO LOCK." INDICATE IN FBC
 CHAPTER 10 WHERE THIS IS PERMITTED. SEE FBC 1008.2. NOT
 ENOUGH INFORMATION PROVIDED TO DETERMINE CODE
 COMPLIANCE.
  
 6. OK
  
 NOT ENOUGH ACCURATE INFORMATION PROVIDED TO PROVIDE A
 COMPLETE CHECKLIST. FBC 107
  
  
  
  
  