Plan Review Notes
Plan Review Notes For Permit 13090969
Permit Number 13090969
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-19 10:49:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SIGNAGE TO BE SUBMITTED SEPARATELY (ADVISORY ONLY).
  
 2. NEW FIXTURES SHOWN. NO ELECTRICAL REVIEW HAS BEEN
 DONE AT THIS TIME BUT PLEASE BE ADVISED THAT A SEPARATE
 ELECTRICAL PERMIT (WITH PLANS) WILL BE REQUIRED
 (ADVISORY ONLY).
  
 3. REVISE PLAN TO SHOW OCCUPANCY CLASSIFICATION AND
 OCCUPANT LOAD FOR THE EXISTING BUILDING AND EXTERIOR
 COURTYARD. IT APPEARS THAT THE COURTYARD AREA IS
 CURRENTLY USED AS STORAGE AND WILL NOW BE A2. 1300
 SF/15 IS AN OCCUPANT LOAD OF 87 FOR THE COURTYARD.
 OCCUPANT LOAD OF EXISTING RESTAURANT NOT SHOWN AND
 CANNOT BE DETERMINED AS KITCHEN/BATHROOM/WAITING AREAS
 NOT SHOWN.
  
 PROVIDE A LIFE SAFETY PLAN, FBC CHAPTER 10. EXITING
 STRATEGY NOT CLEAR. A DOOR IS SHOWN AS "EMERGENCY
 EGRESS," EXIT SIGNS SHOWN, BUT EXITING PATH NOT SHOWN.
 SEE ALSO FBC 1008.1.2 AND 1008.1.10. INCLUDE ELEVATION
 CHANGES, IF ANY, WHICH EXIST THROUGHOUT THE PROPOSED
 MEANS OF EGRESS PATH.
  
 4. PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD
 REQUIRED, FAC9N-3, FBC 107 (DOOR). INDICATE HARDWARE
 AND THRESHOLD OPTIONS, SEE FBC 1008.1.10 AND FBC 2010
 ACCESSIBILITY 404.
  
 5. PROVIDE A DETAIL FOR THE PROPOSED GATE. CODE
 REFERENCE AND REQUIREMENTS CANNOT BE PROVIDED AT THIS
 TIME, SEE ITEM 3. IF THERE ARE NO CODE REQUIREMENTS FOR
 THE GATE, THIS MAY NOT BE REQUIRED.
  
 6. TWO COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED, FBC
 107. ONLY ONE SET OF PLANS PROVIDED. THE CRA
 INFORMATION IS NOT REQUIRED FOR PERMITTING.
  
  
  
  
  