Plan Review Notes
Plan Review Notes For Permit 13090955
Permit Number 13090955
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-11-13 10:34:396651 NORTH JOG ROAD - TRANSFORMER ROOM/VAULT
 TRACKING #13090955
 MASTER #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 70 - ARTICL 450: PART III. TRANSFORMER VAULTS
  
 450.42 WALLS, ROOFS, AND FLOORS. THE WALLS AND ROOFS OF
 VAULTS SHALL BE CONSTRUCTED OF MATERIALS THAT HAVE
 ADEQUATE STRUCTURAL STRENGTH FOR THE CONDITIONS WITH A
 MINIMUM FIRE RESISTANCE OF 3 HOURS. THE FLOORS OF
 VAULTS IN CONTACT WITH THE EARTH SHALL BE OF CONCRETE
 THAT IS NOT LESS THAN 4-INCHES THICK, BUT WHERE THE
 VAULT IS CONSTRUCTED WITH A VACANT SPACE OR OTHER
 STORIES BELOW IT, THE FLOOR SHALL HAVE ADEQUATE
 STRUCTURAL STRENGTH FOR THE LOAD IMPOSED THEREON AND A
 MINIMUM FIRE RESISTANCE OF 3 HOURS. FOR THE PURPOSES OF
 THIS SECTION, STUDS AND WALLBOARD CONSTRUCTION SHALL
 NOT BE ACCEPTABLE.
 EXCEPTION: WHERE TRANSFORMERS ARE PROTECTED WITH
 AUTOMATIC SPRINKLER, WATER SPRAY, CARBON DIOXIDE, OR
 HALON, CONSTRUCTION OF 1-HOUR RATING SHALL BE
 PERMITTED.
  
 (A) TYPE OF DOOR. EACH DOORWAY LEADING INTO A VAULT
 FROM THE BUILDING INTERIOR SHALL BE PROVIDED WITH A
 TIGHT-FITTING DOOR THAT HAS A MINIMUM FIRE RATING OF 3
 HOURS. THE AUTHORITY HAVING JURISDICTION SHALL BE
 PERMITTED TO REQUIRE SUCH A DOOR FOR AN EXTERIOR WALL
 OPENING WHERE CONDITIONS WARRANT.
 EXCEPTION: WHERE TRANSFORMERS ARE PROTECTED WITH
 AUTOMATIC SPRINKLER, WATER SPRAY, CARBON DIOXIDE, OR
 HALON, CONSTRUCTION OF 1-HOUR RATING SHALL BE
 PERMITTED.
  
 (B) SILLS. A DOOR SILL OR CURB THAT IS OF SUFFICIENT
 HEIGHT TO CONFINE THE OIL FROM THE LARGEST TRANSFORMER
 WITHIN THE VAULT SHALL BE PROVIDED, AND IN NO CASE
 SHALL THE HEIGHT BE LESS THAN 4-INCHES.
  
 (C) LOCKS. DOORS SHALL BE EQUIPPED WITH LOCKS, AND
 DOORS SHALL BE KEPT LOCKED, ACCESS BEING ALLOWED ONLY
 TO QUALIFIED PERSONS. PERSONNEL DOORS SHALL SWING OUT
 AND BE EQUIPPED WITH PANIC BARS, PRESSURE PLATES, OR
 OTHER DEVICES THAT ARE NORMALLY LATCHED BUT OPEN UNDER
 SIMPLE PRESSURE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730