| 2013-10-23 10:33:21 | BUILDING PLAN REVIEW |
| | MASTER PERMIT: 12040784 |
| | REVISION # 13090955 PHASED WORK TRANSFORMER ROOM |
| | ADD: 6651 N JOG RDFCONT: KBR |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. OCT. 23/ 2013 |
| | ACTION: BUILDING PROVISO: |
| | MISSING PRODUCT APPROVALS FOR NEW BUILDING A REVISION |
| | IS REQUIRED. |
| | |
| | 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) 010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B), WALL LOUVERS, |
| | (C) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 3) 11/14/2013 THIS ROOM IS A INTERIOR ROOM THE ABOVE |
| | PRODUCT APPROVALS IS NOT REQUIRED, THE CITY'S CHIEF |
| | ELECTRICAL INSPECTOR & PLANS EXAMINER HAS REVIEWED THIS |
| | PLANS, THE SIZE OF THE TRANSFORMERS AND DECLARED IT A |
| | TRANSFORMER VAULT, THAT REQUIRES 3 HR FIRE RATED |
| | FLOORS, WALLS & CEILINGS WITH 2 HOUR OPENING |
| | PROTECTIVES, PLEASE PROVIDE THE 2 HOUR OPENING |
| | PROTECTIVES FOR OPENINGS AND PROVIDE HOW THE STEEL |
| | BEAMS AND COLUMNS THAT MAKE UP THE ENCLOSURE WILL BE |
| | FIRE RATED TO THE 3 HOUR REQUIREMENT. ALSO SEE FIRE |
| | COMMENTSAND REQUIREMENTS FOR A TRANSFORMER VAULT. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |