Plan Review Notes
Plan Review Notes For Permit 13090952
Permit Number 13090952
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-10-09 11:30:20PERMIT #13090952
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET 400-A1.1: PANIC HARDWARE MAY BE NEEDED ON EXIT
 DOORS. PER NFPA 70 ARTICLE 110.26(C)(3): WHERE
 EQUIPMENT RATED 1200A OR MORE THAT CONTAINS OVERCURRENT
 DEVICES, SWITCHING DEVICES, OR CONTROL DEVICES IS
 INSTALLED AND THERE ARE PERSONNEL DOORS INTENDED FOR
 ENTRANCE TO AND EGRESS FROM THE WORKING SPACE LESS THAN
 25 FEET FROM THE NEAREST EDGE OF THE WORKING SPACE, THE
 DOORS SHALL OPEN IN THE DIRECTION OF EGRESS AND BE
 EQUIPPED WITH PANIC BARS, PRESSURE PLATES, OR OTHER
 DEVICES THAT ARE NORMALLY LATCHED BUT OPEN UNDER SIMPLE
 PRESSURE.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  