2013-10-24 19:39:52THE NEC HAS SPECIFIC LIGHTING REQUIREMENTS FOR
 RESIDENTIAL APPLICATIONS WHETHER EXISTING OR NEW, THEY
 ARE NOT REFLECTED ON THE SUBMITTED DRAWINGS. THE 2008
 EDITION OF THE NEC REQUIRES AN OUTLET ON THE BALCONY IF
 GREATER THAN 20 SQ. FT. NEC 406.11 REQUIRES
 TAMPER-RESISTANT RECEPTACLES.
 CORRECT THE ELECTRICAL DRAWINGS TO MEET THE
 REQUIREMENTS AND RESUBMIT, WHILE AT IT, RELOCATE THE
 LIGHT SWITCH AT THE ENTRY FROM BEHIND THE DOOR SWING.
  
 SENT TO SH DESK