| Plan Review Notes For Permit 13090924 |
| Permit Number |
13090924 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-24 19:39:52 | THE NEC HAS SPECIFIC LIGHTING REQUIREMENTS FOR | | | RESIDENTIAL APPLICATIONS WHETHER EXISTING OR NEW, THEY | | | ARE NOT REFLECTED ON THE SUBMITTED DRAWINGS. THE 2008 | | | EDITION OF THE NEC REQUIRES AN OUTLET ON THE BALCONY IF | | | GREATER THAN 20 SQ. FT. NEC 406.11 REQUIRES | | | TAMPER-RESISTANT RECEPTACLES. | | | CORRECT THE ELECTRICAL DRAWINGS TO MEET THE | | | REQUIREMENTS AND RESUBMIT, WHILE AT IT, RELOCATE THE | | | LIGHT SWITCH AT THE ENTRY FROM BEHIND THE DOOR SWING. | | | | | | SENT TO SH DESK |
|