| Plan Review Notes For Permit 13090912 |
| Permit Number |
13090912 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-29 08:41:43 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS | | | FOR THE ADDITION AS REQUIRED BY FBC M1401.3. | | | | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS AND LISTING INFORMATION FOR THE | | | MINI-SPLIT SYSTEM. FBC M1401.1 AND M1302.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|