2013-10-29 08:41:432010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS
 FOR THE ADDITION AS REQUIRED BY FBC M1401.3.
  
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND LISTING INFORMATION FOR THE
 MINI-SPLIT SYSTEM. FBC M1401.1 AND M1302.1
  