| 2013-10-29 07:44:12 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE EXPOSURE CATEGORY "B" SPECIFIED ON SHEET S-1 IS |
| | INCORRECT. THE STRUCTURE IS LOCATED WITHIN 100 FEET OF |
| | A OPEN AREA OF SURFACE ROUGHNESS C-TYPE TERRAIN THAT |
| | EXTENDS MORE THAN 600 FEET AND IS WIDER THAN 150 FEET. |
| | THEREFORE, IT IS EXPOSURE "C". FBC R301.2.1.4.2 AND |
| | R301.2.1.3 |
| | |
| | 2) THE DESIGN PRESSURES IN THE SCHEDULE ON SHEET S-1 |
| | ARE HIGHER THAN IS REQUIRED FOR WALL ZONES 4 AND 5 OF A |
| | DWELLING WITH A 15 FT OR LESS MEAN ROOF HEIGHT LOCATED |
| | IN EXPOSURE C WITH A WIND SPEED OF 170 MPH VULT / 132 |
| | MPH VASD. WALL ZONE 5 PRESSURES FOR 10 SQFT ARE + 38 |
| | PSF, - 51 PSF. SEE FBC TABLES R301.2(2) AND R301.2(3). |
| | |
| | 3) PROVIDE A STRUCTURAL DETAIL FOR THE OPENING IN-FILL |
| | FRAMING. SPECIFY THE ANCHORS AND CONNECTORS. FBC R601.2 |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R806 FOR REQUIRED ROOF |
| | VENTILATION. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R314.3.1 FOR REQUIRED SMOKE |
| | ALARMS. ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 6) THE PROPOSED FLOOR PLAN ON SHEET A-1 SPECIFIES A |
| | FIXED WINDOW AT THE NEW BATHROOM AND THE PROPOSED |
| | WINDOW TYPE IS NOT SPECIFIED FOR THE WINDOW IN THE |
| | STUDY. PRODUCT APPROVALS WERE SUBMITTED FOR A |
| | HORIZONTAL SLIDING WINDOW AND A SINGLE HUNG WINDOW. |
| | PLEASE CLARIFY THE LOCATIONS AND TYPES OF WINDOWS. CITY |
| | AMENDMENTS 107.2.1 |
| | |
| | 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SIMPSON |
| | CONNECTORS SPECIFIED ON THE PLANS. DCA RULE 9N-3 |
| | |
| | 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGN PROFESSIONAL PER |
| | CITY AMENDMENTS 107.3.4.1. |
| | |