Plan Review Notes
Plan Review Notes For Permit 13090906
Permit Number 13090906
Review Stop B
Sequence Number 2
Notes
Date Text
2013-11-21 20:56:05BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
  
 FBC R = 2010 FLORIDA BUILDING CODE - RESIDENTIAL
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
  
 1) FBC R301.1 HEADER BEAM CALCULATION. SUBMITTAL OF THE
 HEADER CALCULATIONS IS NOTED, BUT THEY DO NOT
 COMPLETELY ADDRESS THE BEAM STRENGTH AND HANGER
 QUESTIONS RAISED IN COMMENTS 3 AND 4 OF THE PREVIOUS
 PLAN REVIEW.
 THE SUBMITTED "ENERCALC" HEADER BEAM CALCULATION
 REFERENCES ASCE 7-02, INSTEAD OF THE CURRENT FBC
 REFERENCED ASCE 7-10, AND THE UNIFORM LOADS DO NOT
 APPEAR TO ACCOUNT FOR THE HORIZONTAL WIND LOAD OF 42
 PSF APPLIED OVER A TRIBUTARY WIDTH OF 5.8 FEET (HALF
 THE HEIGHT OF THE DOOR AND TRANSOM WINDOW), APPLIED AT
 THE SAME TIME AS THE STATED 120 PLF VERTICAL LOAD FROM
 THE TRANSOM WINDOW. NO HORIZONTAL LOAD SEEMS TO HAVE
 BEEN APPLIED IN THIS CALCULATION. PLEASE CORRECT CODE
 REFERENCE TO ASCE 7-10 AND CHECK THE BEAM STRESSES,
 HANGER CAPACITY, AND TAPCON CAPACITY, FOR THE COMBINED
 HORIZONTAL (WIND) AND VERTICAL LOADS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]