| Plan Review Notes For Permit 13090906 |
| Permit Number |
13090906 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-17 11:32:45 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE DESIGN PARAMETERS AND REQUIRED OPENING | | | PRESSURES ON THE REVISED DRAWING. THE WINDSPEED IS 170 | | | MPH VULT AND THE EXPOSURE CATEGORY IS C. FBC R301.2.1 | | | | | | 2) SPECIFY THE DIMENSIONS OF THE OPENING ABOVE AND | | | BELOW THE PROPOSED HEADER. CITY AMENDMENTS 107.2.1 | | | | | | 3) PROVIDE STRUCTURAL CALCULATIONS TO SHOW THAT THE | | | DOUBLE (2)-2X6 HEADER IN THE HORIZONTAL ORIENTATION | | | SHOWN IN THE SECTION A-A CAN SUPPORT THE WEIGHT OF THE | | | WINDOW ABOVE WITH OUT SAGGING AND PLACING A LOAD ON THE | | | DOOR FRAME BELOW. ALSO CONSIDER THE LOADS TRANSFERED | | | FROM THE 5"-4" X 3'-5" F.G. TRANSOM WINDOW ABOVE (FL# | | | 7630-R4) AND THE 3' X 8' FRENCH DOOR WITH A 24" | | | SIDELITE (NOA NO. 11-1110.15) THAT IS ANCHORED TO IT | | | FROM BELOW. CITY AMENDMENTS 107.2.1.3 | | | | | | 4) THE TWO SIMPSON H4 HURRICANE CLIPS THAT ARE | | | SPECIFIED TO SECURE THE HEADER AT EACH END ARE NOT | | | DESIGNED OR TESTED FOR THIS APPLICATION. IF YOU WISH TO | | | USE THESE UNDER ALTERNATE METHODS AND MATERIALS, | | | PROVIDE SIGNED AND SEALED CALCULATIONS, RATIONAL | | | ANALYSIS OR OTHER DATA TO SUPPORT YOUR PROPOSAL. THE | | | INFORMATION WILL BE REVIEWED AND A DETERMINATION WILL | | | BE MADE BY THE BUILDING OFFICIAL. CITY AMENDMENTS | | | 104.11.2 AND FBC 1712.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|