Plan Review Notes
Plan Review Notes For Permit 13090906
Permit Number 13090906
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-17 11:32:452010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE DESIGN PARAMETERS AND REQUIRED OPENING
 PRESSURES ON THE REVISED DRAWING. THE WINDSPEED IS 170
 MPH VULT AND THE EXPOSURE CATEGORY IS C. FBC R301.2.1
  
 2) SPECIFY THE DIMENSIONS OF THE OPENING ABOVE AND
 BELOW THE PROPOSED HEADER. CITY AMENDMENTS 107.2.1
  
 3) PROVIDE STRUCTURAL CALCULATIONS TO SHOW THAT THE
 DOUBLE (2)-2X6 HEADER IN THE HORIZONTAL ORIENTATION
 SHOWN IN THE SECTION A-A CAN SUPPORT THE WEIGHT OF THE
 WINDOW ABOVE WITH OUT SAGGING AND PLACING A LOAD ON THE
 DOOR FRAME BELOW. ALSO CONSIDER THE LOADS TRANSFERED
 FROM THE 5"-4" X 3'-5" F.G. TRANSOM WINDOW ABOVE (FL#
 7630-R4) AND THE 3' X 8' FRENCH DOOR WITH A 24"
 SIDELITE (NOA NO. 11-1110.15) THAT IS ANCHORED TO IT
 FROM BELOW. CITY AMENDMENTS 107.2.1.3
  
 4) THE TWO SIMPSON H4 HURRICANE CLIPS THAT ARE
 SPECIFIED TO SECURE THE HEADER AT EACH END ARE NOT
 DESIGNED OR TESTED FOR THIS APPLICATION. IF YOU WISH TO
 USE THESE UNDER ALTERNATE METHODS AND MATERIALS,
 PROVIDE SIGNED AND SEALED CALCULATIONS, RATIONAL
 ANALYSIS OR OTHER DATA TO SUPPORT YOUR PROPOSAL. THE
 INFORMATION WILL BE REVIEWED AND A DETERMINATION WILL
 BE MADE BY THE BUILDING OFFICIAL. CITY AMENDMENTS
 104.11.2 AND FBC 1712.1
  