Plan Review Notes
Plan Review Notes For Permit 13090901
Permit Number 13090901
Review Stop E
Sequence Number 1
Notes
Date Text
2013-10-24 18:26:23APPROVED WITH THE FOLLOWING EXCEPTIONS:
 1. QUOTE THE CURRENT EDITION OF THE NEC FOR COMPLIANCE
 (NEC 2008)
 2. PRIMARY OCPD AND WIRING NOT CORRECT FOR THE 30KVA
 TRANSFORMER
 3. THOUGH COMPLETE FIRE ALARM DRAWINGS HAVE NOT BEEN
 SUBMITTED, IT IS UNDERSTOOD THAT THE EXISTING SYSTEM IS
 CAPABLE OF SUPPORTING THE ADDITIONAL DEVICES AND
 MAINTAIN ADEQUATE COMPLIANCE.
 4. BECAUSE THE EXISTING FIRE ALARM SYSTEM'S WIRING IS
 BEING INTERRUPTED AND/OR ALTERED A CERTIFICATE OF TEST
 WILL BE REQUIRED FOR FINAL INSPECTION.