| Plan Review Notes For Permit 13090901 |
| Permit Number |
13090901 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-24 18:26:23 | APPROVED WITH THE FOLLOWING EXCEPTIONS: | | | 1. QUOTE THE CURRENT EDITION OF THE NEC FOR COMPLIANCE | | | (NEC 2008) | | | 2. PRIMARY OCPD AND WIRING NOT CORRECT FOR THE 30KVA | | | TRANSFORMER | | | 3. THOUGH COMPLETE FIRE ALARM DRAWINGS HAVE NOT BEEN | | | SUBMITTED, IT IS UNDERSTOOD THAT THE EXISTING SYSTEM IS | | | CAPABLE OF SUPPORTING THE ADDITIONAL DEVICES AND | | | MAINTAIN ADEQUATE COMPLIANCE. | | | 4. BECAUSE THE EXISTING FIRE ALARM SYSTEM'S WIRING IS | | | BEING INTERRUPTED AND/OR ALTERED A CERTIFICATE OF TEST | | | WILL BE REQUIRED FOR FINAL INSPECTION. |
|