| Plan Review Notes For Permit 13090835 |
| Permit Number |
13090835 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-21 11:03:18 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM | | | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) | | | | | | APPLICATION STATES SHUTTERS ARE EXISTING, BUT I WAS | | | UNABLE TO LOCATE A PERMIT FOR THE SHUTTERS. PROVIDE A | | | PERMIT NUMBER. | | | | | | 2. A PLAN WAS SUBMITTED PREPARED BY JMS DESIGN INC. | | | ARCHITECTURE. DOCUMENTS PREPARED BY AN ARCHITECT AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS FS481. | | | | | | 3. PROVIDE BUILDING HEIGHT. DESIGN PRESSURES FOR | | | BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING | | | ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER | | | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED | | | ORIGINALS FAC61G15-23.002. | | | | | | 4. FLORIDA STATE OR LOCAL PRODCUT APPROVAL REQUIRED, | | | FAC9N-3. PROVIDE FLORIDA STATE PRODUCT APPROVAL COVER | | | SHEET FOR PROPOSED DOORS. | | | | | | | | | |
|