| 2013-10-19 12:03:28 | BUILDING PLAN REVIEW |
| | PERMIT: 13090825 |
| | ADD: 1155 BELVEDERE RD |
| | CONT: TO BE DETERMINED/ FRITZ MASSON |
| | TEL: (954)710-1118 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SATURDAY OCT. 19/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S1.01 STRUCTURAL DESIN / WIND DESIGN CRITERIA |
| | INDICATES A BUILDING RISK CATEGORY I WITH WIND AT VULT |
| | 155 MPH/ 3 SECOND GUST. PLEASE REFER TO THE 2010 FBC-B |
| | TABLE 1604.5 RISK CATEGORY I BUILDINGS INCLUDE MINOR |
| | STORAGE FACILITIES, SHEDS, AGRICULTURAL FACILITIES & |
| | SCREEN ENCLOSURES. PLEASE UPDATE WIND DESIGN CRITEIA |
| | AND ASSOCIATED PRESSURES. |
| | |
| | 1604.5.1 MULTIPLE OCCUPANCIES. |
| | WHERE A BUILDING OR STRUCTURE IS OCCUPIED BY TWO OR |
| | MORE OCCUPANCIES NOT INCLUDED IN THE SAME RISK |
| | CATEGORY, IT SHALL BE ASSIGNED THE CLASSIFICATION OF |
| | THE HIGHEST RISK CATEGORY CORRESPONDING TO THE VARIOUS |
| | OCCUPANCIES. WHERE BUILDINGS OR STRUCTURES HAVE TWO OR |
| | MORE PORTIONS THAT ARE STRUCTURALLY SEPARATED, EACH |
| | PORTION SHALL BE SEPARATELY CLASSIFIED. WHERE A |
| | SEPARATED PORTION OF A BUILDING OR STRUCTURE PROVIDES |
| | REQUIRED ACCESS TO, REQUIRED EGRESS FROM OR SHARES LIFE |
| | SAFETY COMPONENTS WITH ANOTHER PORTION HAVING A HIGHER |
| | RISK CATEGORY, BOTH PORTIONS SHALL BE ASSIGNED TO THE |
| | HIGHER RISK CATEGORY. |
| | |
| | 2) UPDATE THE WIND LOAD/ PRESSURE CHART, THIS CHART |
| | DOES NOT INDICATE IF THE AREA AFFECTED IS 10 SF, 20, |
| | 50, OR 100 SF. NOR HEIGHT ADJUSTMENT FACTORS. 2010 |
| | FBC-B TABLE 1609. |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) 2 010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 5) SHEET S2.01 DETAIL # 14 TOWER DETAIL INDICATES THE |
| | STEEL STUD WALL SECTION BEING TIED DOWN TO THE 2X |
| | SOLLID BLOCKING BETWEEN THE JOIST BUT NO TIE DOEN TO |
| | THE CONCRETE WALL BENEATH, PART OF THE MWFRT, MAIN WIND |
| | FORCE RESISTING SYSSTEM. |
| | |
| | JAMES A. WITMER CBO |