| Plan Review Notes For Permit 13090810 |
| Permit Number |
13090810 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-23 09:14:05 | FAILED | | | | | | 1) REPEAT COMMENT: NO SURVEY WAS PROVIDED. | | | | | | 2) REPEAT COMMENT: THE SITE PLAN IS INADEQUATE AS IT | | | DOES NOT SHOW DIMENSIONS FROM THE PROPOSED GENERATOR | | | AND PAD TO THE PROPERTY LINES AND EXISTING STRUCTURES. | | | ADDITIONALLY, THE SITE PLAN DOES NOT DESIGNATE WHERE | | | THE NEW GENERATOR PAD, AS REFERENCED ON SHEET E.4 IS | | | LOCATED. ALL THAT IS REFERENCED IS AN AREA LABELED ?NEW | | | ELECTRICAL STUB UP AREA? | | | | | | 3) REPEAT COMMENT: THE GENERATOR IS SHOWN AT 8.25 FEET | | | IN HEIGHT, NOT INCLUDING THE ENGINE EXHAUST WITH RAIN | | | CAP. THE GENERATOR SHALL BE SCREENED FOR ITS FULL | | | HEIGHT BY AN OPAQUE WALL/FENCE WITH GATE AND LANDSCAPE. | | | NO PLANS WERE SUBMITTED TO SHOW EITHER EXISTING OR | | | PROPOSED SCREENING. PLEASE NOTE THAT IF THE EXISTING | | | FENCE AND LANDSCAPE MEET THIS STANDARD, THEN NO | | | ADDITIONAL SCREENING IS REQUIRED. GOOGLE STREET VIEW | | | DOES NOT PROVIDE VERIFICATION THAT THE EXISTING IS | | | ADEQUATELY SCREENED. | | | | | | 4) MORE COMMENTS MAY BE GENERATED WHEN COMPLETE PLANS | | | ARE SUBMITTED. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | 2014-04-09 11:52:18 | 4/9/14 RESUB ZONING, SENT TO ES.SG |
|