| 2013-10-16 09:56:24 | THE FOLLOWING ITEMS NEED TO BE ADDRESS FOR A | | | SATISFACTORY ELECTRICAL REVIEW: | | | 1. MUST PROVIDE A SERVICE RISER DIAGRAM TO INCLUDE ANY | | | SUB PANELS IF ANY. RISER DIAGRAM SHALL INDICATE WIRE | | | SIZE AND PROPER GROUNDING. | | | 2. MUST INDICATE THE LOCATION OF THE EXISTING PANEL | | | BEFORE THE REMODEL. | | | 3. ELECTRICAL NOTES ADDRESS NEW A/C UNITS. THE | | | ELECTRICAL CONNECTIONS TO IT SHALL BE INDICATED ON | | | PLANS. | | | 4. PROVIDE THE REQUIRED ILLUMINATION FOR THE RELOCATED | | | SPIRAL STAIRS TO COMPLY W/FBC 2010 | | | 5. NEW OPENINGS TO THE POOL AREA SHALL BE PROPERLY | | | PROTECTED WITH POOL ALARMS AS REQUIRED. | | | 6. SHOW DISTANCE FROM RESIDENCE TO THE POOL WATER EDGE. | | | SENT BACK TO BIN BY: MA |
|