| 2013-10-28 08:20:15 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE NUMBERING OF THE PLAN SHEETS INDICATE THAT |
| | SHEETS 1 AND 3 ARE MISSING. PLEASE SUBMIT MISSING |
| | SHEETS. CITY AMENDMENTS 107.2.1 |
| | |
| | 2) PROVIDE AREA CALCULATIONS ON THE PLANS. SPECIFY |
| | EXISTING CONDITIONED LIVING SPACE AND PROPOSED |
| | CONDITIONED LIVING SPACE. CITY AMENDMENTS 107.2.1.3 |
| | |
| | 3) PROVIDE AN EXTERIOR OPENING IN-FILL STRUCTURAL |
| | DETAIL. CITY AMENDMENTS 107.2.1 |
| | |
| | 4) THE ULTIMATE WIND SPEED OF 160 MPH LISTED ON SHEET 4 |
| | IS INCORRECT. THE CITY OF WEST PALM BEACH HAS AN |
| | ULTIMATE WIND SPEED OF 170 MPH. FBC FIGURE R301.2(4) |
| | |
| | 5) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE |
| | ADDED LIVING SPACE AS REQUIRED BY FBC ENERGY |
| | CONSERVATION SECTION 101.4.3. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R314.3.1 FOR SMOKE ALARMS |
| | IN THE DWELLING UNIT. |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R318 FOR PROTECTION AGAINST |
| | TERMITES. |
| | |
| | 8) SHOW COMPLIANCE WITH FBC R806 FOR REQUIRED ROOF |
| | VENTILATION. |
| | |
| | 9) SHOW COMPLIANCE WITH FBC R807 FOR REQUIRED ATTIC |
| | ACCESS. |
| | |
| | 10) THE SECOND FLOOR GUARDRAIL HEIGHT IS SPECIFIED AS |
| | 3'-6" ON SHEET 5 AND 36" ON SHEET 7. PLEASE CLARIFY. |
| | FBC R312.2 AND CITY AMENDMENTS 107.2.1 |
| | |
| | 11) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR |
| | THE GIRDER TRUSS THAT WILL CARRY THE NEW BALCONY FLOOR |
| | TRUSSES SHOWN ON SHEET 7. FBC R802.1.6.5 |
| | |
| | 12) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE NEW BALCONY FLOOR TRUSSES TO THE 2 X 12 WALL LEDGER |
| | SHOWN ON SHEET 7. FBC R802.1.6.5 |
| | |
| | 13) THE CROSS SECTION ON SHEET 7 APPEARS TO CONFLICT |
| | WITH THE ROOF FRAMING PLAN FOR THE ORIENTATION OF THE |
| | ROOF TRUSSES. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 |
| | |
| | 14) THE DETAIL FOR THE GABLE END FRAMING ON SHEET 7 |
| | SHOWS 2 X 12 RAFTERS WITH A 2 X 12 BEAM BELOW IT |
| | SUPPORTED BY A 4 X 4 POST. THIS CONDITION DOES NOT |
| | APPEAR ON THE PLANS. PLEASE CLARIFY. |
| | |
| | 15) PROVIDE A FRAMING DETAIL OR RAKE BEAM DETAIL FOR |
| | THE GABLE END AT THE RIGHT ELEVATION. FBC R601.2 |
| | |
| | 16) SUBMIT TWO COPIES OF A SURVEY / SITE PLAN THAT |
| | INDICATES THE SEPARATION DISTANCE FROM THE PROPERTY |
| | LINES. FBC R302.1 |
| | |
| | 17) SUBMIT A SURFACE DRAINAGE PLAN THAT SHOWS |
| | COMPLIANCE WITH FBC R401.3. |
| | |
| | 18) SUBMIT TWO COPIES OF CURRENT PRODUCT APPROVALS FOR |
| | THE METAL ROOF FL# 11175.1, THE POLYGLASS SELF ADHESIVE |
| | UNDERLAYMENT, THE CASEMENT WINDOWS FL# 245.2, THE |
| | SLIDING GLASS DOOR FL# 251.6, THE CERTAINTEED MODIFIED |
| | ROOFING FL# 2533.1, THE 8" LINTELS AND THE SIMPSON |
| | CONNECTORS. MARK THE SPECIFIC ASSEMBLY AND ITS DESIGN |
| | PRESSURES FOR THE ITEM YOU WILL USE IN THE PRODUCT |
| | APPROVAL AND MAKE SURE THAT THE DESIGN PRESSURES YOU |
| | SELECT ARE GREATER THAN THE REQUIRED PRESSURES |
| | SPECIFIED ON THE PLANS. DCA RULE 9N-3 |
| | |
| | 19) CITY AMENDMENT 107.3.4.1 REQUIRES THE DESIGNER OF |
| | RECORD OF THE PROJECT TO REVIEW AND APPROVE THE PRODUCT |
| | APPROVALS IN WRITING. SPECIFICATION OF THE PRODUCT |
| | APPROVALS ON THE SIGNED AND SEALED PLANS MEETS THIS |
| | REQUIREMENT. |
| | |
| | 20) THE SYSTEM NUMBERS SPECIFIED IN THE PRODUCT |
| | APPROVAL AFFIDAVIT ON SHEET 4 (ALSO ON SHEET 7) FOR THE |
| | CERTAINTEED ROOFING FL 2533.1 HAS THE WRONG SYSTEM |
| | NUMBERS LISTED. W-39 IS A SELF ADHERING SYSTEM AND W-42 |
| | AND W-44 ARE HYBIRD SYSTEMS WITH DIFFERENT BASE SHEETS. |
| | ALSO THE SPECIFIED DESIGN PRESSURES LISTED DO NOT |
| | CORRESPOND TO THESE SYSTEMS. PLEASE CORRECT. |
| | |
| | 21) PROVIDE WINDOW AND DOOR BUCK ATTACHMENT DETAILS ON |
| | THE PLANS. FBC R612.10.2 |
| | |
| | NOTE: PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW |
| | THE REVIEW COMMENTS HAVE BEEN ADDRESSED. THIS WILL HELP |
| | TO EXPEDITE YOUR NEXT REVIEW. |
| | |