Plan Review Notes
Plan Review Notes For Permit 13090807
Permit Number 13090807
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-28 08:20:152010 FBC
  
 DENIED BY BUILDING
  
 1) THE NUMBERING OF THE PLAN SHEETS INDICATE THAT
 SHEETS 1 AND 3 ARE MISSING. PLEASE SUBMIT MISSING
 SHEETS. CITY AMENDMENTS 107.2.1
  
 2) PROVIDE AREA CALCULATIONS ON THE PLANS. SPECIFY
 EXISTING CONDITIONED LIVING SPACE AND PROPOSED
 CONDITIONED LIVING SPACE. CITY AMENDMENTS 107.2.1.3
  
 3) PROVIDE AN EXTERIOR OPENING IN-FILL STRUCTURAL
 DETAIL. CITY AMENDMENTS 107.2.1
  
 4) THE ULTIMATE WIND SPEED OF 160 MPH LISTED ON SHEET 4
 IS INCORRECT. THE CITY OF WEST PALM BEACH HAS AN
 ULTIMATE WIND SPEED OF 170 MPH. FBC FIGURE R301.2(4)
  
 5) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDED LIVING SPACE AS REQUIRED BY FBC ENERGY
 CONSERVATION SECTION 101.4.3.
  
 6) SHOW COMPLIANCE WITH FBC R314.3.1 FOR SMOKE ALARMS
 IN THE DWELLING UNIT.
  
 7) SHOW COMPLIANCE WITH FBC R318 FOR PROTECTION AGAINST
 TERMITES.
  
 8) SHOW COMPLIANCE WITH FBC R806 FOR REQUIRED ROOF
 VENTILATION.
  
 9) SHOW COMPLIANCE WITH FBC R807 FOR REQUIRED ATTIC
 ACCESS.
  
 10) THE SECOND FLOOR GUARDRAIL HEIGHT IS SPECIFIED AS
 3'-6" ON SHEET 5 AND 36" ON SHEET 7. PLEASE CLARIFY.
 FBC R312.2 AND CITY AMENDMENTS 107.2.1
  
 11) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR
 THE GIRDER TRUSS THAT WILL CARRY THE NEW BALCONY FLOOR
 TRUSSES SHOWN ON SHEET 7. FBC R802.1.6.5
  
 12) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE NEW BALCONY FLOOR TRUSSES TO THE 2 X 12 WALL LEDGER
 SHOWN ON SHEET 7. FBC R802.1.6.5
  
 13) THE CROSS SECTION ON SHEET 7 APPEARS TO CONFLICT
 WITH THE ROOF FRAMING PLAN FOR THE ORIENTATION OF THE
 ROOF TRUSSES. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 14) THE DETAIL FOR THE GABLE END FRAMING ON SHEET 7
 SHOWS 2 X 12 RAFTERS WITH A 2 X 12 BEAM BELOW IT
 SUPPORTED BY A 4 X 4 POST. THIS CONDITION DOES NOT
 APPEAR ON THE PLANS. PLEASE CLARIFY.
  
 15) PROVIDE A FRAMING DETAIL OR RAKE BEAM DETAIL FOR
 THE GABLE END AT THE RIGHT ELEVATION. FBC R601.2
  
 16) SUBMIT TWO COPIES OF A SURVEY / SITE PLAN THAT
 INDICATES THE SEPARATION DISTANCE FROM THE PROPERTY
 LINES. FBC R302.1
  
 17) SUBMIT A SURFACE DRAINAGE PLAN THAT SHOWS
 COMPLIANCE WITH FBC R401.3.
  
 18) SUBMIT TWO COPIES OF CURRENT PRODUCT APPROVALS FOR
 THE METAL ROOF FL# 11175.1, THE POLYGLASS SELF ADHESIVE
 UNDERLAYMENT, THE CASEMENT WINDOWS FL# 245.2, THE
 SLIDING GLASS DOOR FL# 251.6, THE CERTAINTEED MODIFIED
 ROOFING FL# 2533.1, THE 8" LINTELS AND THE SIMPSON
 CONNECTORS. MARK THE SPECIFIC ASSEMBLY AND ITS DESIGN
 PRESSURES FOR THE ITEM YOU WILL USE IN THE PRODUCT
 APPROVAL AND MAKE SURE THAT THE DESIGN PRESSURES YOU
 SELECT ARE GREATER THAN THE REQUIRED PRESSURES
 SPECIFIED ON THE PLANS. DCA RULE 9N-3
  
 19) CITY AMENDMENT 107.3.4.1 REQUIRES THE DESIGNER OF
 RECORD OF THE PROJECT TO REVIEW AND APPROVE THE PRODUCT
 APPROVALS IN WRITING. SPECIFICATION OF THE PRODUCT
 APPROVALS ON THE SIGNED AND SEALED PLANS MEETS THIS
 REQUIREMENT.
  
 20) THE SYSTEM NUMBERS SPECIFIED IN THE PRODUCT
 APPROVAL AFFIDAVIT ON SHEET 4 (ALSO ON SHEET 7) FOR THE
 CERTAINTEED ROOFING FL 2533.1 HAS THE WRONG SYSTEM
 NUMBERS LISTED. W-39 IS A SELF ADHERING SYSTEM AND W-42
 AND W-44 ARE HYBIRD SYSTEMS WITH DIFFERENT BASE SHEETS.
 ALSO THE SPECIFIED DESIGN PRESSURES LISTED DO NOT
 CORRESPOND TO THESE SYSTEMS. PLEASE CORRECT.
  
 21) PROVIDE WINDOW AND DOOR BUCK ATTACHMENT DETAILS ON
 THE PLANS. FBC R612.10.2
  
 NOTE: PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW
 THE REVIEW COMMENTS HAVE BEEN ADDRESSED. THIS WILL HELP
 TO EXPEDITE YOUR NEXT REVIEW.
  