Plan Review Notes
Plan Review Notes For Permit 13090772
Permit Number 13090772
Review Stop B
Sequence Number 2
Notes
Date Text
2013-10-31 19:29:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. PREVIOUS REVIEWER'S COMMENTS NOT ADDRESSED. A SEALED
 SURVEY WAS SUBMITTED. THIS IS NOT THE SAME AS SIGNED
 SEALED STRUCTURAL DRAWING WHICH INCLUDES WIND DESIGN
 CRITERIA FBC 1603.1.4.
  
 IF SIGNED AND SEALED STRUCTURAL ARE NOT PROVIDED,
 CALCULATIONS SHOWING RESISTANCE TO WIND LOADS ARE
 REQUIRED AS WELL AS THE PRINTED NAME AND SIGNATURE OF
 THE INDIVIDUAL TAKING REPONSIBILITY FOR THE DESIGN, FBC
 107.
  
 2. SCOPE NOT CLEAR. APPLICATION STATES THAT A NEW
 MONUMENT WILL BE INSTALLED, PLAN SHOWS MODIFICATION TO
 EXISTING. PLEASE CORRELATES.
  