Plan Review Notes
Plan Review Notes For Permit 13090744
Permit Number 13090744
Review Stop B
Sequence Number 1
Notes
Date Text
2013-09-28 10:33:082010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SURVEY AND A SITE PLAN
 SHOWING THE LOCATION OF THE PROPOSED ADDITION.
  
 2) THE PLANS SPECIFY THAT THE FOOTING, STEM WALL AND
 SLAB ARE EXISTING, HOWEVER, THE PROPERTY APPRAISER'S
 RECORDS DO NOT SHOW ANYTHING AT THE AREA OF THIS
 PROPOSED ADDITION. THE BUILDING DEPARTMENT RECORDS DO
 NOT INDICATE THAT THIS WORK WAS PERMITTED OR INSPECTED.
 A PERMIT FOR AN ADDITION (PERMIT # 07060979) WAS
 APPLIED FOR BY THE OWNER IN 2007. THIS PERMIT WAS NEVER
 ISSUED AND HAS EXPIRED. PROVIDE EVIDENCE THAT THE
 FOOTING, STEM WALL AND SLAB WERE PERMITTED AND PASSED
 INSPECTIONS. OTHERWISE THEY SHALL BE REMOVED OR
 EVALUATED BY A STRUCTURAL ENGINEER TO THE SATISFACTION
 OF THE CITY OF WEST PALM BEACH'S BUILDING DIVISION.
 CITY AMENDMENTS 109.4 & SECTION 114
  
 3) FBC R314.3.1 REQUIRES SMOKE ALARMS TO BE INSTALLED
 AS REQUIRED FOR NEW DWELLINGS WHEN ADDITIONS OR
 ALTERATIONS REQUIRING PERMITS OCCUR. SHOW COMPLIANCE.
  
 4) THE PLANS SHOW A 2" X 6" RAFTERS IN A SINGLE ROOF /
 CEILING ASSEMBLY WITH R-30 INSULATION. R-30 BATT
 INSULATION IS 9.5" TO 10" THICK DEPENDING ON THE BRAND.
 A 2 X 6 WILL ONLY PROVIDE 5.5" OF SPACE BETWEEN THE
 CEILING AND ROOF SHEATHING, WHICH IS NOT ENOUGH SPACE
 FOR THE INSULATION AND AN AIR SPACE. PLEASE CORRECT.
 NOTE. THE ENERGY CALCULATION FORM REQUIRES A MINIMUM OF
 R-30 INSULATION. FBC ENERGY CONSERVATION 402.1
  
 5) FORM 402-2010 SPECIFIES CERTAIN PERFORMANCE CRITERIA
 THAT MUST BE MET. THE EXTERIOR WALL INSULATION FOR
 FRAME IS REQUIRED TO BE R-13 AND R-11 IS SPECIFIED ON
 THE FORM. R-11 IS INCORRECTLY SPECIFIED ON THE FORM FOR
 CONCRETE OR MASONRY " MASS" WALLS, THIS ADDITION DOES
 NOT HAVE EXTERIOR CONCRETE OR MASONRY WALLS. THERE ARE
 NO WALLS THAT ARE "ADJACENT" TO UNCONDITIONED SPACE.
 PLEASE CORRECT. FBC ENERGY CONSERVATION 402.1
  
 6) THE MAXIMUM DESIGN NEGATIVE PRESSURE FOR THE WINDOW
 IS SPECIFIED AS - 50 PSF ON THE PRODUCT APPROVAL
 (FL5418) AND THE REQUIRED NEGATIVE PRESSURE SPECIFIED
 ON THE PLAN IS -50.61 PSF. THE DESIGN PRESSURES FOR THE
 WINDOW ARE REQUIRED EXCEED THE REQUIRED PRESSURES. FBC
 R301.2.1
  
 7) THE PLANS SPECIFY A SIMONTON "STORM BREAKER" SERIES
 WINDOW AND THE PRODUCT APPROVAL EVALUATION AND
 INSTALLATION INSTRUCTIONS IS FOR THE "SAFEPOINT"
 SERIES. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 8) THE PRODUCT APPROVAL FOR THE TAMKO MODIFIED ROOFING
 SYSTEM NOA NO. 12-0716.18 HAS BEEN REPLACED BY NOA NO.
 12-1003.05. PLEASE SUBMIT THE CURRENT PRODUCT APPROVAL
 THAT HAS BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. DCA RULE 9N-3 AND CITY AMENDMENTS
 107.3.4.1
  
 9) SPECIFY THE APPROVED ASSEMBLY, THE FASTENING OPTION
 AND THE MINIMUM DESIGN PRESSURES THAT WILL BE USED TO
 INSTALL THE TAMKO ROOFING SYSTEM. PROVIDE TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING FOR THE PERIMETER AND CORNER ROOF AREAS, AS
 REQUIRED BY LIMITATION #7 ON THE LAST PAGE OF THE NOA.
 FBC R905.1
  
 10) THE VALUE FOR THE WORK SPECIFIED ON THE APPLICATION
 OF $1500.00 IS TOO LOW. FOR PERMITTING FEE PURPOSES THE
 VALUE IS TO BE THE TOTAL REPLACEMENT VALUE INCLUDING
 STRUCTURAL, ELECTRICAL, DESIGN FEES, OVERHEAD AND
 PROFIT AS WOULD BE CHARGED BY A CONTRACTOR. PLEASE
 PROVIDE AN ACCURATE CONSTRUCTION COST VALUE. CITY
 AMENDMENTS 109.3
  
 11) IN ORDER TO SPEED PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]