| Plan Review Notes For Permit 13090717 |
| Permit Number |
13090717 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-17 09:05:25 | SHEET E1.0 INDICATES #6 ISOLATED GROUND FROM XFORMER | | | AND BETWEEN PANELBOARDS. PLEASE INDICATE METHODS OF | | | COMPLIANCE WITH 250.30, 250 PART III, 250.58, 250.104, | | | PROVIDE STROBES IN BATHROOMS. PLANS NOTED AND APPROVED. | | | GIVEN TO J WITMER. |
|