| Plan Review Notes For Permit 13090696 |
| Permit Number |
13090696 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-11-30 15:40:46 | BUILDING PROVISO ROOFING: | | | A SEPERATE ROOFING PERMIT, REVIEW WITH ASSOCIATED FEES | | | WILL BE REQUIRED. | | | SUBMITTED NOA 12-0625.02 | | | FIRESTONE ULTRA PLY TPO & TPO XR SINGLE PLY ROOF | | | SYSTEMS OVER STEEL DECKS. | | | NO SUB-SYSTEM IS HIGHLIGHTED. A-141- A-143 ROOF DECK | | | INDICATES THE USE OF A FFIRESTONE SINGLE PLY SYSTEM, | | | THE PERIMETER (ZONES 2 & 3) TO BE FULLY ADHERED, THE | | | INTERIOR ZONE # 1 TO BE MECHANICALLY FASTENED. NONE OF | | | THE SUB-SYSTEMS LISTED IN THE 63 PAGE REPORT ARE | | | IDENTIFIED. PLEASE NOTE BOTH LIMITATION # 7 AND | | | LIMITATION # 9 BOTH OCCUR IN THIS REPORT. WHEN THE | | | SUB-SYSTEMS ARE IDENTIFIED AND IF LIMITATION #7 DOES | | | REQUIRE ENHANCED FASTENING IN ZONES 2 & 3 A DESIGN | | | PROFESSIONAL WILL NEED TO PRODUCE THE FASTENING | | | SCHEDULE USING RAS 117. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|