2013-10-31 16:04:34PERMIT #13090696
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 **** FAIL COMMENTS********
 1) SHEET A112, TENANT SPACE A3: PER NFPA 101, 7.4.1.2
 (2) - REQUIRES NOT LESS THAN FOUR (4) MEANS OF EGRESS
 WHERE THE OCCUPANT LOAD EXCEEDS 1000 PERSONS.
  
 2) EGRESS WIDTH NOT PROVIDED ON PLANS.
  
 ****PROVISO*******
 PLAN SUBMITTED IS FOR BUILDING SHELL, ONLY. ADDITIONAL
 REQUIREMENTS MAY NEED TO BE MET UPON REVIEW OF TENAT
 LAYOUT/PLANS.
  
 ADDITIONAL FIRE EXTINGUISHERS MAY BE NEEDED PENDING
 FIELD INSPECTION.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  