| 2013-10-31 16:04:34 | PERMIT #13090696 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | **** FAIL COMMENTS******** | | | 1) SHEET A112, TENANT SPACE A3: PER NFPA 101, 7.4.1.2 | | | (2) - REQUIRES NOT LESS THAN FOUR (4) MEANS OF EGRESS | | | WHERE THE OCCUPANT LOAD EXCEEDS 1000 PERSONS. | | | | | | 2) EGRESS WIDTH NOT PROVIDED ON PLANS. | | | | | | ****PROVISO******* | | | PLAN SUBMITTED IS FOR BUILDING SHELL, ONLY. ADDITIONAL | | | REQUIREMENTS MAY NEED TO BE MET UPON REVIEW OF TENAT | | | LAYOUT/PLANS. | | | | | | ADDITIONAL FIRE EXTINGUISHERS MAY BE NEEDED PENDING | | | FIELD INSPECTION. | | | | | | ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A | | | LOCK/UNLOCK INDICATOR. | | | | | | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH | | | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL | | | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | | SPACED NOT MORE THAN 15 FEET ON CENTER. | | | | | | SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE | | | FIRE ALARM AND SPRINKLER SYSTEM. | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|