Plan Review Notes
Plan Review Notes For Permit 13090696
Permit Number 13090696
Review Stop E
Sequence Number 1
Notes
Date Text
2013-11-06 15:07:25THOUGH THE SCOPE OF THIS PERMIT IS LIMITED TO SHELL
 STRUCTURE FOR TENANT BUILD-OUT, WHATEVER MINIMUM
 ELECTRIC SERVICE IS BEING PROVIDED SHALL BE DESCRIBED
 AND THUS PRESENTED ON THE PLANS FOR REVIEW.
 PG. E001 REFLECTS PANEL HVA (NEW) & PANEL LVA (NEW)
 SERVICED FROM TRANSFORMER #3 AND PAGE E002 SHOWS THREE
 DIFFERENT RISER DIAGRAMS INDICATING THEIR RESPECTIVE
 TERMINATIONS, BUT NO PANEL SCHEDULES ARE PROVIDED FOR
 EACH.
 PLEASE MAKE THE APPROPRIATE CORRECTIONS AND RESUBMIT
 FOR REVIEW.
  
  