Plan Review Notes
Plan Review Notes For Permit 13090696
Permit Number 13090696
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-26 14:08:09BUILDING PLAN REVIEW
 PERMIT:13090696
 ADD: 1875 PALM BEACH LAKES BLDG "A"
 CONT: TO BE DETERMINED
 TEL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: OCT. 26/ 2013
 ACTION: DENIED
  
 1) ) PB OUTLET MALLS:A LETTER FROM THE QUALIFIER OF
 BOTH THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT
 BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT
 BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 2) THIS JOB WILL REQUIRE A RESIDENT INSPECTOR SINCE
 TILT-UP CONSTRUCTION AND BEING TYPE II CONSTRUCTION.
 PLEASE CONTACT THE MANAGER OF THE RESIDENT INSPECTOR
 PROGRAM KEN CONRAD FOR THE REQUIRED INFORMATION AND
 PAPERWORK THAT WILL NEED TO BE FILED. 110.3.9. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012
 KEN CONRAD MANAGER OF RESIDENT INSPECTOR PROGRAM
 TEL: (561) 805-6666
 E-MAIL: [email protected]
 THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE
 BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109.
 HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO
 THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE
 CALLED FOR BY ANY PROVISION OF THE TECHNICAL
 CODES SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE
 SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE.
  
 3) WITH THE REQUIREMENT OF A RESIDENT INSPECTOR, (3)
 SETS OF PLANS AND DOCUMENTS WILL BE REQUIRED BEFORE
 PERMIT ISSUANCE. ONE FOR THE FIELD, ONE FOR THE
 RESIDENT INSPECTOR AND ONE ON FILE WITHIN THE BUILDING
 DEPARTMENT.
  
 4) MISSING SOILS REPORT BY ECS COMPLETED JUNE 16/2012
 PROJECT # 25-1847-C. 1803.5.2 QUESTIONABLE SOIL.
  
 5) COVER-SHEET PLANS INDICATE THE OCCUPANT LOAD AND THE
 REQUIRED EGRESS WIDTH PER OCCUPANT AT 0.2" / OCCUPANT
 FBC-B 1005.1 BUT THE PLANS LACK WHAT WIDTH IS PROVIDED
 NOR WIDTH REQUIRED.
  
 6) SHEET A112 THE LIFE SAFETY SHEET FOR TENANT SPACE A3
 THE OCCUPANT LOAD IS 1170, THE REQUIRED DOOR WIDTH OF
 19.5' IS MET WITH 21' PROVIDED, THE ISSUE IS BECAUSE OF
 THE OCCUPANT LOAD BEING OVER 1000 FBC-B TABLE 1021.1
 REQUIRES 4 EXITS.
  
 7) S002 DETAIL #7 INDICATES THE USE OF 5/8 INCH CDX
 PLYWOOD , THIS A TYPE IIB BUILDING 603.1.1 ONLY ALLOWS
 FOR THE USE OF FIRE RETARDANT TREATED PLYWOOD.
  
 8) SHEET S004 DETAIL FOR FOUNDATION EMBEDS INDICATES
 THE USE OF EMBEDS FOR TILT-WAL CONSTRUCTION BUT S-101
 DOES NOT PROVIDE THE LOCATION WHERE THE EMBEDS ARE TO
 BE PLACED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
 THE EMBEDS ARE PART OF THE MWFRS MAIN WIND FORCE
 RESISTING SYSTEM.
  
 9) SHEET A141;
 A/C UNIT # 6 IS WITH IN 10'-0 OF THE EDGE OF THE ROOF
 FBC-B 1013.5 MECHANICAL EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS., ROLL UP, SWING, SLIDING,
 METAL, LOUVER
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES AND ROOFING
 INSULATION
 (E)
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 12) FOR EACH OF THE VARIOUS PRODUCT APPROVALS LISTED
 ABOVE PLEASE INDICATE WHICH TYPE OF GLAZING, OR ROOFING
 SUBSYSTEM IS TO BE INSTALLED, CIRCLE TO IDENTIFY THE
 SYSTEM, AND ASSOCIATED PRESSURES.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676