2013-10-26 12:55:31BUILDING PLAN REVIEW
 PERMIT:13090695
 ADD: 1845 PALM BEACH LAKES BLDG "C" WHOLE FOODS"
 CONT: TO BE DETERMINED
 TEL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: OCT. 26/ 2013
 ACTION: DENIED
  
 1) THE INFORMATION DESCRIBING THIS PROJECT IS NOT CLEAR
 AS TO IF THIS IS A SHELL ONLY PERMIT OR IF THIS IS A
 COMPLETE BUILDING BEING BUILT FOR WHOLE FOODS? THIS
 REVIEW WILL ASSUME IT IS A SHELL PERMIT ONLY!!!
  
 2) PB OUTLET MALLS:A LETTER FROM THE QUALIFIER OF BOTH
 THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT
 BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT
 BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 3) THIS JOB WILL REQUIRE A RESIDENT INSPECTOR SINCE
 TILT-UP CONSTRUCTION AND BEING TYPE II CONSTRUCTION.
 PLEASE CONTACT THE MANAGER OF THE RESIDENT INSPECTOR
 PROGRAM KEN CONRAD FOR THE REQUIRED INFORMATION AND
 PAPERWORK THAT WILL NEED TO BE FILED. 110.3.9. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012
 KEN CONRAD MANAGER OF RESIDENT INSPECTOR PROGRAM
 TEL: (561) 805-6666
 E-MAIL: [email protected]
 THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE
 BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109.
 HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO
 THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE
 CALLED FOR BY ANY PROVISION OF THE TECHNICAL
 CODES SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE
 SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE.
  
 4) WITH THE REQUIREMENT OF A RESIDENT INSPECTOR, (2)
 SETS OF PLANS AND DOCUMENTS WILL BE REQUIRED BEFORE
 PERMIT ISSUANCE. ONE FOR THE FIELD, ONE FOR THE
 RESIDENT INSPECTOR.
  
 5) MISSING SOILS REPORT BY ECS COMPLETED JUNE 16/2012
 PROJECT # 25-1847-C. 1803.5.2 QUESTIONABLE SOIL.
  
 6) COVER SHEET INDICATE THE OCCUPANT LOAD AND THE
 REQUIRED EGRESS WIDTH PER OCCUPANT AT 0.2" / OCCUPANT
 FBC-B 1005.1 BUT THE PLANS LACK WHAT WIDTH IS PROVIDED
 NOR WIDTH REQUIRED.
  
 7) S002 DETAIL #7 INDICATES THE USE OF 5/8 INCH CDX
 PLYWOOD , THIS A TYPE IIB BUILDING 603.1.1 ONLY ALLOWS
 FOR THE USE OF FIRE RETARDANT TREATED PLYWOOD.
  
 8) SHEET S004 DETAIL FOR FOUNDATION EMBEDS INDICATES
 THE USE OF EMBEDS FOR TILT-WAL CONSTRUCTION BUT S-101
 DOES NOT PROVIDE THE LOCATION WHERE THE EMBEDS ARE TO
 BE PLACED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
 THE EMBEDS ARE PART OF THE MWFRS MAIN WIND FORCE
 RESISTING SYSTEM.
  
 9) SHEET A141;
 A) THE ROOF HATCH IS LOCATED WITHIN 10'-0" OF THE EDGE
 OF THE ROOF PLEASE PROVIDE COMPLIANCE WITH FBC-B 1013.6
 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 B) THE RTU-7 LOCATION THE PLANS INDICATE RECEIVING/
 ENCLOSED DOCK, IS THIS A SRIBNERS ERROR?
  
 C) RTU-2 INDICATES EXIT VESTIBULE, PLEASE PROVIDE
 ADDITIONAL INFORMATION, FBC-B 107.2.1.3.
  
 10) SHEET A-601 DOOR SCHEDULE AND FIRE RATINGS PLEASE
 REVIEW 2010 FBC-B TABLE 715.4 IS IN MINUTES & HOURS.
  
 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 12) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS., ROLL UP, SWING, SLIDING,
 METAL, LOUVER
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES AND ROOFING
 INSULATION
 (E)
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 13) FOR EACH OF THE VARIOUS PRODUCT APPROVALS LISTED
 ABOVE PLEASE INDICATE WHICH TYPE OF GLAZING, OR ROOFING
 SUBSYSTEM IS TO BE INSTALLED, CIRCLE TO IDENTIFY THE
 SYSTEM, AND ASSOCIATED PRESSURES.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  