| 2013-10-03 14:14:34 | BUILDING PLAN REVIEW |
| | PERMIT: 13090684 |
| | ADD: 1741 PALM BEACH LAKES # E239 |
| | CONT: TO BE DETERMINED |
| | TEL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: OCT. 03/2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2.0 & A2.2 FLOOR PLAN INDICATE THE 2ND EXIT |
| | THROUGH THE STOCK ROOM. 2010 FBC-B TABLE 1015.1 |
| | REQUIRES A SECOND EXIT SINCE THE OCCUPANT LOAD FOR THE |
| | MERCANTILE OCCUPANCY IS OVER 49. PLEASE PROVIDE |
| | COMPLIANCE WITH: |
| | 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES. |
| | EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| | THIS SECTION. |
| | 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| | ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| | EXCEPTIONS: |
| | 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| | FOLLOWING ARE MET: |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION |
| | THAT WILL MAINTAIN THE REQUIRED WIDTH AND LEAD DIRECTLY |
| | FROM THE RETAIL AREA TO THE EXIT WITHOUT OBSTRUCTIONS. |
| | |
| | PB OUTLET MALLS: |
| | BUILDING PROVISO: |
| | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |