| Plan Review Notes For Permit 13090669 |
| Permit Number |
13090669 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-11-27 12:22:17 | SENT TO SH DESK | | 2013-11-27 12:21:28 | PROVISIOS: | | | 1. THE SCOPE OF THIS PERMIT IS AS INDICATED ON THE | | | PERMIT APPLICATION, TO REMOVE AND REPLACE BROKEN METER | | | SOCKET AND RISER PIPE. IF THE REMOVAL OF THE METER | | | SOCKET CREATES A SITUATION WHERE THE FEEDERS MUST BE | | | REPLACED, THE NEW WIRING, REGARDLESS OF WHAT IS | | | EXISTING, SHALL BE IN ACCORDANCE WITH THE CURRENT | | | EDITION OF THE NEC. | | | 2. ALL GROUNDING SYSTEM SHALL BE REPLACED AND MADE | | | CURRENT, INCLUDING THE INSTALLATION OF THE INTER-SYSTEM | | | BONDING TERMINAL REQUIRED BY NEC 250.94. | | | 3. ALL WORK SHALL COMPLY WITH ALL REQUIREMENTS OF THE | | | 2008 EDITION OF THE NEC AND IS SUBJECT TO THE APPROVAL | | | OF THE FIELD INSPECTOR. | | 2013-11-27 11:54:52 | THE CONTRACTOR CALLED IN THIS MORNING ALLEGING THAT | | | DOUG HAD ALREADY SIGNED OFF ON THIS PERMIT, BUT THE | | | RECORDS DO NOT REFLECT SUCH. I WILL ONCE AGAIN LOOK AT | | | THE SUBMITTAL AND EVALUATE THE CIRCUMSTANCES. |
|