| Plan Review Notes For Permit 13090669 |
| Permit Number |
13090669 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-26 15:08:16 | 13090669 | | | 4000 GREEN WOOD | | | NEW ELECTRIC SERVICE | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | SHOW LOCATION OF ALL SERVICE DISCONNECTS. A BUILDING OR | | | OTHER STRUCTURE SERVED SHALL BE SUPPLIED BY ONLY ONE | | | SERVICE. MAIN DISCONNECTS ARE REQUIRED TO BE GROUPED IN | | | ONE LOCATION. NEC 230.2 | | | | | | SERVICE CONDUCTORS NEED TO BE RATED FOR WET LOCATION. | | | NEC 310.10 | | | | | | INDICATE THE SIZE, RATING, AND LOCATION OF THE EXISTING | | | PANEL BOARDS. INDICATE SIZE OF PANEL FEEDERS. NEC 215.5 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS. FBC R313 | | | | | | A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC | | | 250.94 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | | | | |
|