| Plan Review Notes For Permit 13090656 |
| Permit Number |
13090656 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-28 10:07:20 | 4310 BROADWAY | | | PERMIT #13090656 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | WHAT IS THE OCCUPANT LOAD FOR THIS SPACE? PER NFPA 101 | | | SECTION 7.2.1.4.2, DOORS ARE REQUIRED TO SWING IN THE | | | DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50 | | | OR GREATER PERSONS. | | | | | | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE | | | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, | | | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, | | | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE | | | EGRESS SIDE. | | | | | | PER NFPA 101 SECTION 7.2.1.5.9, THE LOCK/LATCH | | | RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR | | | WITH NOT MORE THAN ONE RELEASING OPERATION. THE | | | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF | | | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING | | | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF | | | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE | | | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST | | | TO OPERATE. | | | | | | THE EXISTING FLOOR PLAN DOES NOT SHOW ANY REAR WINDOWS; | | | HOWEVER, THE NEW FLOOR PLANS INDICATE THREE NEW REAR | | | WINDOWS. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|