Plan Review Notes
Plan Review Notes For Permit 13090640
Permit Number 13090640
Review Stop M
Sequence Number 1
Notes
Date Text
2013-10-19 09:15:27PLANS DENIED
 1) CONDENSERS ON ROOF. REFER TO SECTION 304.11
 GUARDS 2010 FBC (M) PLAN SHOWS PARAPET IF PARAPET
 MEATS THE REQUIREMENTS OF SECTION 314.11 GUARDS
 ARE NOT REQUIRED.
 2) PAGE A302 DOOR FRAME SCHEDULE SHOW WOOD
 DOORS ON AIRHANDLER CLOSET. REFER TO SECTION 602.2.1
 MATERIALS WITHIN PLENUM'S. 2010 FBC )M)
 3) PAGE M2.1 OF PLAN SHOW BATHROOM EXHAUST
 UP TO CAP.TO ROOF IS MARKED OFF. REFER TO SECTION
 501.2.11 LOCATION OF EXHAUST OUTLETS AND SECTION
 501.2.1.1 EXHAUST DISCHARGE 2010 FBC (M)
 4) CURB DETAIL #6 ON PAGE A250 OF PLAN SHOW
 A WOOD DECK, CURB DETAIL ON PAGE M7.1 SHOWS
 CONCRETE.PLEASE CLARIFY. PROVIDE A DETAIL FROM THE
 ENGINEER ON THE CONDENSER STAND TO ROOF TIEDOWN
 AND CONDENSER TO STAND TIEDOWN ( PROVIDE BOLT SIZE
 WITH DETAIL )
 5) PROVIDE ENERGY CALCULATIONS WITH PLAN. PER
 SECTION 503.2.1 FLORIDA ENERGY CODE 2010