Plan Review Notes
Plan Review Notes For Permit 13090640
Permit Number 13090640
Review Stop E
Sequence Number 1
Notes
Date Text
2013-12-30 10:44:00THE INTENT OF THIS REVIEW IS NOT TO GENERATE A PUNCH
 LIST FOR THE DESIGN PROFESSIONAL, BUT ON THE FIRST
 REVIEW THE FOLLOWING DEFICIENCIES WERE NOTED:
 1. PAGE E2.1
 A. AS PER NEC 110.26(D), ILLUMINATION IS REQUIRED FOR
 THE ELECTRICAL ROOMS AS WELL AS FOR THE FIRE RISER
 CLOSET.
 2. PAGE 2.2 & 2.3
 A. THE EXIT SIGN DO NOT INDICATE THAT THEY ARE VISIBLE
 FROM BOTH SIDES.
 3. PAGE E4.1 TYPICAL UNIT LIGHTING PLAN
 A. UNIT A1:
 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN
 THE BALCONY
 2. AS PER NEC 110.26(D), THERE SHALL BE ILLUMINATION IN
 FRONT OF THE ELECTRICAL PANEL
 B. UNIT B1
 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN
 THE BALCONY
 C. UNIT C1
 1. AS PER NEC 210.70(A)(1), RE SHALL BE A LIGHT IN THE
 BALCONY
 2. PAGE 4.2 TYPICAL UNIT POWER PLAN, NEC 406.11
 REQUIRES TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS
 A. OUTLET PLACEMENT SHALL BE IN ACCORDANCE TO NEC
 210.52.
 B. NOT THAT IT IS NOT INCORRECT OR IMPROPER, BUT WITH
 PROPER PLACEMENT THERE IS AN UNREQUIRED SMOKE DETECTOR
 IN UNITS A1 & B1
 C. RELOCATE THE SMOKE DETECTOR OF UNIT A1 TO COMPLY
 WITH NFPA 29.8.3.4
 5. PAGE 6.1 PANEL SCHEDULES
 A. MUST PROVIDE VOLTAGE DROP CALCULATIONS FOR FEEDERS
 B. AS PER NEC 210.12 ARC-FAULT CIRCUIT INTERRUPTION IS
 REQUIRED IN DWELLING UNITS.
  
 THOUGH A SEPARATE FIRE ALARM PERMIT SHALL BE REQUIRED
 AND THE NECESSARY DOCUMENTATION FOR SAME SHALL
 ACCOMPANY SUCH PERMIT, A PRELIMINARY REVIEW OF THE
 PLACEMENT OF THE INITIATING DEVICES ON THE SECOND &
 THIRD FLOOR SHOULD BE RELOCATED TO COMPLY WITH NFPA 72
 SECTION 17.14.6
  
 IF YOU HAVE ANY QUESTIONS WITH REGARDS TO ANY OF THESE
 COMMENTS, PLEASE DO NOT HESITATE TO CONTACT ME.
 MIKE ALBARRAN, ELECTRICAL PLANS REVIEWER (561) 805-6718
  