| 2013-12-30 10:44:00 | THE INTENT OF THIS REVIEW IS NOT TO GENERATE A PUNCH |
| | LIST FOR THE DESIGN PROFESSIONAL, BUT ON THE FIRST |
| | REVIEW THE FOLLOWING DEFICIENCIES WERE NOTED: |
| | 1. PAGE E2.1 |
| | A. AS PER NEC 110.26(D), ILLUMINATION IS REQUIRED FOR |
| | THE ELECTRICAL ROOMS AS WELL AS FOR THE FIRE RISER |
| | CLOSET. |
| | 2. PAGE 2.2 & 2.3 |
| | A. THE EXIT SIGN DO NOT INDICATE THAT THEY ARE VISIBLE |
| | FROM BOTH SIDES. |
| | 3. PAGE E4.1 TYPICAL UNIT LIGHTING PLAN |
| | A. UNIT A1: |
| | 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN |
| | THE BALCONY |
| | 2. AS PER NEC 110.26(D), THERE SHALL BE ILLUMINATION IN |
| | FRONT OF THE ELECTRICAL PANEL |
| | B. UNIT B1 |
| | 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN |
| | THE BALCONY |
| | C. UNIT C1 |
| | 1. AS PER NEC 210.70(A)(1), RE SHALL BE A LIGHT IN THE |
| | BALCONY |
| | 2. PAGE 4.2 TYPICAL UNIT POWER PLAN, NEC 406.11 |
| | REQUIRES TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS |
| | A. OUTLET PLACEMENT SHALL BE IN ACCORDANCE TO NEC |
| | 210.52. |
| | B. NOT THAT IT IS NOT INCORRECT OR IMPROPER, BUT WITH |
| | PROPER PLACEMENT THERE IS AN UNREQUIRED SMOKE DETECTOR |
| | IN UNITS A1 & B1 |
| | C. RELOCATE THE SMOKE DETECTOR OF UNIT A1 TO COMPLY |
| | WITH NFPA 29.8.3.4 |
| | 5. PAGE 6.1 PANEL SCHEDULES |
| | A. MUST PROVIDE VOLTAGE DROP CALCULATIONS FOR FEEDERS |
| | B. AS PER NEC 210.12 ARC-FAULT CIRCUIT INTERRUPTION IS |
| | REQUIRED IN DWELLING UNITS. |
| | |
| | THOUGH A SEPARATE FIRE ALARM PERMIT SHALL BE REQUIRED |
| | AND THE NECESSARY DOCUMENTATION FOR SAME SHALL |
| | ACCOMPANY SUCH PERMIT, A PRELIMINARY REVIEW OF THE |
| | PLACEMENT OF THE INITIATING DEVICES ON THE SECOND & |
| | THIRD FLOOR SHOULD BE RELOCATED TO COMPLY WITH NFPA 72 |
| | SECTION 17.14.6 |
| | |
| | IF YOU HAVE ANY QUESTIONS WITH REGARDS TO ANY OF THESE |
| | COMMENTS, PLEASE DO NOT HESITATE TO CONTACT ME. |
| | MIKE ALBARRAN, ELECTRICAL PLANS REVIEWER (561) 805-6718 |
| | |