| Plan Review Notes For Permit 13090639 |
| Permit Number |
13090639 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-12-26 11:35:12 | THE FOLLOWING CORRECTIONS HAVE TO BE ADDRESSED FOR A | | | SUCCESSFUL ELECTRICAL REVIEW: | | | 1. THE VARIOUS LIGHTING PLANS DO NOT REFLECT THE | | | REQUIRED LIGHTING INSIDE THE FIRE RISER & STORAGE | | | CLOSETS AS WELL AS IN THE ELEVATOR EQUIPMENT ROOM. | | | 2. PAGES E4.1 & 4.2 REFER TO TYPE "D" UNITS BUT FOR A | | | TOWNHOUSE BLDG., THE PLANS TO NOT MATCH THE REMAINDER | | | OF THE PACKET. | | | 3. INDIVIDUAL UNIT BALCONY LIGHTING IS NOT REFLECTED ON | | | PLANS. | | | 4. REGARDLESS OF OUTLET SPACING AS INDICATED ON THE | | | APPROVED DRAWINGS, ACTUAL FIELD PLACEMENT OF THE | | | OUTLETS IS SUBJECT TO FIELD INSPECTOR'S APPROVAL. | | | 5. ON THE RISER DIAGRAMS AND PANEL SCHEDULES IT APPEARS | | | THAT THE FEEDER FOR "MCA" WAS NOT ADJUSTED AS PER | | | NEC310.15(B) | | | | | | THOUGH A SEPARATE DRAWING SHALL BE SUBMITTED AND PERMIT | | | SECURED FOR THE FIRE ALARM, PLEASE REVIEW THEW | | | PLACEMENT OF THE INITIATING DEVICES AS SUBMITTED, AS | | | WELL AS THE ADDITION OF A REMOTE ANNUNCIATOR ADJACENT | | | TO THE ELEVATORS FOR FIRST RESPONDER EASE OF RESPONSE. |
|