| 2013-12-17 14:41:43 | THE INTENT OF THIS REVIEW IS NOT TO GENERATE A PUNCH |
| | LIST FOR THE DESIGN PROFESSIONAL, BUT ON THE FIRST |
| | REVIEW THE FOLLOWING DEFICIENCIES WERE NOTED: |
| | 1. PAGE E2.1 |
| | A) AS PER NEC 110.26(D), ILLUMINATION IS REQUIRED FOR |
| | THE ELECTRICAL ROOMS AS WELL AS FOR THE FIRE RISER |
| | CLOSET. |
| | 2. PAGE 2.2 & 2.3 |
| | A) THE EXIT SIGN DO NOT INDICATE THAT THEY ARE VISIBLE |
| | FROM BOTH SIDES. |
| | 3. PAGE E4.1 TYPICAL UNIT LIGHTING PLAN |
| | A. UNIT A: |
| | 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN |
| | THE BALCONY |
| | 2. AS PER NEC 110.26(D), THERE SHALL BE ILLUMINATION IN |
| | FRONT OF THE ELECTRICAL PANEL |
| | B. UNIT B |
| | 1. AS PER NEC 210.70(A)(1), RE SHALL BE A LIGHT IN THE |
| | BALCONY |
| | 2. I SUGGEST THAT FOR BOTH, ENERGY CONSERVATION AS WELL |
| | AS CONVENIENCE THAT 3 WAY SWITCHING BE PROVIDED FOR THE |
| | LIVING ROOM. |
| | C. UNIT C |
| | 1. AS PER NEC 210.70(A)(1), RE SHALL BE A LIGHT IN THE |
| | BALCONY |
| | 2. I SUGGEST THAT FOR BOTH, ENERGY CONSERVATION AS WELL |
| | AS CONVENIENCE THAT 3 WAY SWITCHING BE PROVIDED FOR THE |
| | LIVING ROOM & CORRIDOR |
| | 4. PAGE 4.2 TYPICAL UNIT POWER PLAN |
| | A. INDICATE THE SCALE USED FOR THESE DRAWINGS. WITHOUT |
| | A SCALE DESIGNATION, PROPER RECEPTACLE AND SMOKE |
| | DETECTOR PLACEMENT IS NOT VERIFIABLE. |
| | B. NOT THAT IT IS INCORRECT OR IMPROPER, BUT WITH |
| | PROPER PLACEMENT THERE IS AN UNREQUIRED SMOKE DETECTOR |
| | IN UNITS A & C. |
| | C. RELOCATE THE SMOKE DETECTOR OF UNIT B TO THE BEDROOM |
| | CORRIDOR |
| | D. NEC 406.11 REQUIRES ?TAMPER-RESISTANT ? RECEPTACLES |
| | IN DWELLING UNITS |
| | 5. PAGE 6.1 PANEL SCHEDULES |
| | A. MUST PROVIDE VOLTAGE DROP CALCULATIONS FOR FEEDERS |
| | B. AS PER NEC 210.12 ARC-FAULT CIRCUIT INTERRUPTION IS |
| | REQUIRED IN DWELLING UNITS. |
| | |
| | THOUGH A SEPARATE FIRE ALARM PERMIT SHALL BE REQUIRED |
| | AND THE NECCESSARY DOCUMENTATION FOR SAME SHALL |
| | ACCOMPANY SUCH PERMIT, A PRELIMINARY REVIEW OF THE |
| | PLACEMENT OF THE INITIATING DEVICES ON THE SECOND & |
| | THIRD FLOOR SHOULD BE RELOCATED TO COMPLY WITH NFPA 72 |
| | SECTION 17.14.6 |
| | |
| | IF YOU HAVE ANY QUESTIONS WITH REGARDS TO ANY OF THESE |
| | COMMENTS, PLEASE DO NOT HESITATE TO CONTACT ME. |
| | MIKE ALBARRAN, ELECTRICAL PLANS REVIEWER (561) 805-6718 |
| | |