| Notes |
| Date |
Text |
| 2013-10-19 10:04:23 | PLAN DENIED | | | 1) CONDENSERS ON ROOF. REFER TO SECTION 304.11 | | | GUARDS 2010 FBC (M). PLAN SHOWS PARAPET IF | | | PARAPET MEATS THE REQUIREMENTS OF SECTION 314.11 | | | GUARDS ARE NOT REQUIRED. | | | 2) PAGE A 302 DOOR FRAME SCHEDULE SHOW WOOD | | | DOORS ON AIR HANDLER CLOSET. REFER TO SECTION | | | 602.2.1 MATERIALS WITHIN PLENUM'S 2010 FBC (M) | | | 3) CURB DETAIL # 6 ON PAGE A 250 SHOW A WOOD DECK. | | | CURB DETAIL ON PAGE M7.1 SHOW CONCRETE .PLEASE CLARIFY | | | PROVIDE A DETAIL FROM THE ENGINEER ON THE CONDENSER | | | STAND TO ROOF TIEDOWN AND CONDENSER TO STAND TIEDOWN. | | | 4) PROVIDE ENERGY CALCULATIONS WITH PLANS. PER SECTION | | | 503.2.1 FLORIDA ENERGY CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805=6676 |
|