| 2014-01-02 15:29:00 | THE INTENT OF THIS REVIEW IS NOT TO GENERATE A PUNCH |
| | LIST FOR THE DESIGN PROFESSIONAL, BUT ON THE FIRST |
| | REVIEW THE FOLLOWING DEFICIENCIES WERE NOTED: |
| | 1 PAGE E2.1 |
| | A. AS PER NEC 110.26(D), ILLUMINATION IS REQUIRED FOR |
| | THE ELECTRICAL ROOMS AS WELL AS FOR THE FIRE RISER |
| | CLOSET. |
| | 2. PAGE 2.2 & 2.3 |
| | 3. PAGE 3.1 ALL OUTLETS IN RESIDENTIAL COMMON AREAS |
| | SHOULD BE "TAMPER RESISTANT" AS WELL |
| | A. THE EXIT SIGN DO NOT INDICATE THAT THEY ARE VISIBLE |
| | FROM BOTH SIDES. AS PER NEC 110.26(D), THE METER ROOM |
| | HAS TO HAVE ILLUMINATION. THERE SHALL BE ILLUMINATION |
| | INSIDE THE OTHER CLOSETS WHICH HAVE EQUIPMENT, AND IN |
| | THE FIRE RISER AND STORAGE CLOSETS. |
| | 4. PAGE E4.1 TYPICAL UNIT LIGHTING PLAN ALL CEILING FAN |
| | BOXES SHALL BE RATED FOR 50#'S AS PER NEC 314.27(A) |
| | A. UNIT A: |
| | 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN |
| | THE BALCONY |
| | 2. AS PER NEC 110.26(D), THERE SHALL BE ILLUMINATION IN |
| | FRONT OF THE ELECTRICAL PANEL |
| | B. UNIT C: |
| | 1. AS PER NEC 210.70(A)(1), THERE SHALL BE A LIGHT IN |
| | THE BALCONY |
| | 2. THERE SHOULD BE A 3 WAY SWITCH FOR THE CORRIDOR |
| | C. UNIT D: |
| | 1. AS PER NEC 210.70(A)(1), RE SHALL BE A LIGHT IN THE |
| | BALCONY |
| | 2. MISSING LIGHT SWITCH FOR M. BATH. |
| | 5.. PAGE 4.2 OUTLET PLACEMENT SHALL BE IN ACCORDANCE TO |
| | NEC 210.52. |
| | B. NOT THAT IT IS NOT INCORRECT OR IMPROPER, BUT WITH |
| | PROPER PLACEMENT THERE IS AN UNREQUIRED SMOKE DETECTOR |
| | IN EACH UNIT. |
| | 6. PAGE 6.1 PANEL SCHEDULES |
| | A. MUST PROVIDE VOLTAGE DROP CALCULATIONS FOR FEEDERS |
| | |
| | |
| | THOUGH A SEPARATE FIRE ALARM PERMIT SHALL BE REQUIRED |
| | AND THE NECESSARY DOCUMENTATION FOR SAME SHALL |
| | ACCOMPANY SUCH PERMIT, A PRELIMINARY REVIEW OF THE |
| | PLACEMENT OF THE INITIATING DEVICES ON THE SECOND & |
| | THIRD FLOOR SHOULD BE RELOCATED TO COMPLY WITH NFPA 72 |
| | SECTION 17.14.6 |
| | |
| | IF YOU HAVE ANY QUESTIONS WITH REGARDS TO ANY OF THESE |
| | COMMENTS, PLEASE DO NOT HESITATE TO CONTACT ME. |
| | MIKE ALBARRAN, ELECTRICAL PLANS REVIEWER (561) 805-6718 |
| | |