| 2014-03-04 11:22:24 | PASS PROVISO | | | 1) SOME DUCT IS MARKED WITH 25 CFM. | | | REVISE FLEX SCHEDULE ON PAGE M6.1 | | | TO INCLUDE DUCT SIZE FOR 25 CFM. | | | 2) DETAIL #6 PAGE M7.1 PROVIDE | | | THE SIZE OF CONCRETE ANCHOR USED. | | | 3) DETAIL #3 PAGE M7.2 PROVIDE | | | THE SIZE ANCHOR USED ON THE PLAN. | | | HAVE REVISION COMPLETED BY 1ST INSPECTION. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|