| 2013-12-09 16:26:13 | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR A SUCCESSFUL |
| | ELECTRICAL REVIEW AS WELL AS FOR A FIRE ALARM REVIEW. |
| | |
| | PAGE E4.1, UNIT A2 |
| | 1. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY |
| | AS PER NEC 210.70 |
| | |
| | UNIT TH, 1ST FLOOR |
| | 1. AD A 3 WAY SWITCH TO EXTINGUISH LIGHTING AS YOU |
| | ENTER THE STAIRS |
| | 2. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY |
| | AS PER NEC 210.70 |
| | |
| | UNIT TH, 2ND FLOOR |
| | 1. MISSING LIGHT & SWITCH FOR CORRIDOR. |
| | |
| | UNIT E |
| | 1. MISSING LIGHT SWITCH ADJACENT TO ENTRY DOOR. |
| | 2. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY |
| | AS PER NEC 210.70 |
| | 3. RELOCATE LIGHT SWITCH TOWARDS ENTRY DOOR OF MASTER |
| | BEDROOM |
| | |
| | UNIT E1 |
| | 1. RELOCATE LIGHT SWITCH TOWARDS ENTRY DOOR OF MASTER |
| | BEDROOM |
| | |
| | UNIT E2 |
| | 1. RELOCATE LIGHT SWITCH TOWARDS ENTRY DOOR OF MASTER |
| | BEDROOM |
| | 2. MISSING THE REQUIRED LIGHT & SWITCH FOR THE BALCONY |
| | AS PER NEC 210.70 |
| | |
| | PAGE 4.2, UNIT A2 |
| | 1. AS PER NEC 210.52(D)(3), THERE HAS TO BE AN OUTLET |
| | ON THE BALCONY |
| | |
| | UNIT E |
| | 1. LINEAR WALL SPACE IN THE LIVING ROOM REQUIRES AN |
| | ADDITIONAL OUTLET AS PER NEC 210.52 |
| | |
| | UNIT TH 1ST FLOOR |
| | 1. AS PER NEC 210.52, AN OUTLET IS MISSING IN THE >2' |
| | AREA BEHIND THE ENTRY DOOR. |
| | 2. RELOCATE THE OUTLETS TO CORRECT SPACING REQUIREMENTS |
| | OF NEC 210.52 |
| | |
| | UNIT E1 & E2 |
| | 1. LINEAR WALL SPACE IN THE LIVING ROOM REQUIRES AN |
| | ADDITIONAL OUTLET AS PER NEC 210.52 |
| | |
| | PAGE E6.1 |
| | THOUGH PERMITTED BY CODE, IT IS MY OPINION THAT IN THE |
| | INTEREST OF LIFE SAFETY THE SMOKE DETECTORS BE |
| | CONNECTED TO A GENERAL LIGHTING CIRCUIT TO MAKE IT |
| | OBVIOUS OF A TRIPPED BREAKER UNLESS THE DEVICES HAS A |
| | MAIN POWER FAILURE WARNING SIGNAL |
| | |
| | PAGE FA2.1 |
| | 1. INTERIOR FIRE WARNING DEVICE IS MISSING FROM INSIDE |
| | THE SECOND BEDROOM OF UNIT E |
| | |
| | |