| Plan Review Notes For Permit 13090630 |
| Permit Number |
13090630 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-16 14:33:39 | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | A UNISEX RESTROOM WILL BE REQUIRED AS THERE ARE MORE | | | THAN AN AGGREGATE OF SIX OR MORE MALE AND FEMALE WATER | | | CLOSETS. | | | 403.5 UNISEX TOILET AND BATHING ROOMS. | | | IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE | | | UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE | | | OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS | | | REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE | | | WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE | | | OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET | | | ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE | | | SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE | | | UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED | | | WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE | | | INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED | | | IN AN OCCUPANCY. | | | | | | ***PROVISO*** | | | FBC PLUMBING 301.6 | | | ELEVATOR SUMP PUMPS ARE REQUIRED TO BE INDIRECTLY | | | CONNECTED TO THE SANITARY. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|