Plan Review Notes
Plan Review Notes For Permit 13090630
Permit Number 13090630
Review Stop M
Sequence Number 1
Notes
Date Text
2013-11-07 14:27:05PLAN DENIED
 1) ROOF MOUNTED EXHAUST DETAIL # 2 PAGE
 M7.1. REFER TO SECTION 501.2.2 EXHAUST OPENING
 PROTECTION.
 2) PROVIDE ENERGY CALCULATION PER SECTION
 503.2.1 FLORIDA ENERGY CODE.2010
 3) REFER TO SECTION 107 2010 FBC
 ROOM 104,106,204 AND 206 PAGE
 M2.1 AND M2.2 PLANS TO HARD TO READ
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  