2014-01-03 13:48:20BUILDING PLAN REVIEW
 PERMIT:13090621
 ADD: 3516 S DIXIE HWY
 CONT: ALLEN GAST
 TEL: (561)833-3535
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 01/03/2014
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET A-1.00 INDICATES THE USE OF FOAM
 SPRAY INSULATION IN THE ATTIC AREA, PLEASE PROVIDE
 PRODUCT TESTING FOR FLAME SPREAD AND PRODUCT
 INSTALATION AND PRODUCT LIMITATIONS PER 2010 FBC-B
 2603.3.ALSO REVIEW 2603.4 THERMAL BARRIER AND 2603.4.1
 & 2603.4.1.1.
 ICC NER-420 ICYNENE REPORT LIST UNDER THE HEADING (4.0)
 LIST 5 APPLICATION TYPES THE DESIGNER OF RECORD WILL
 NEED TO IDENTIFY WHICH SUB-SYSTEM IS TO BE INSTALLED
 FOR THIS PROJECT, DEPENDING OF SUB-SYSTEM SOME MAY
 REQUIRE A IGNITION BARRIER AND OR THEERMAL BARRIER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676