| Plan Review Notes For Permit 13090621 |
| Permit Number |
13090621 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-01-03 13:48:20 | BUILDING PLAN REVIEW | | | PERMIT:13090621 | | | ADD: 3516 S DIXIE HWY | | | CONT: ALLEN GAST | | | TEL: (561)833-3535 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: 01/03/2014 | | | ACTION: DENIED | | | | | | 1) 2ND REQUEST. SHEET A-1.00 INDICATES THE USE OF FOAM | | | SPRAY INSULATION IN THE ATTIC AREA, PLEASE PROVIDE | | | PRODUCT TESTING FOR FLAME SPREAD AND PRODUCT | | | INSTALATION AND PRODUCT LIMITATIONS PER 2010 FBC-B | | | 2603.3.ALSO REVIEW 2603.4 THERMAL BARRIER AND 2603.4.1 | | | & 2603.4.1.1. | | | ICC NER-420 ICYNENE REPORT LIST UNDER THE HEADING (4.0) | | | LIST 5 APPLICATION TYPES THE DESIGNER OF RECORD WILL | | | NEED TO IDENTIFY WHICH SUB-SYSTEM IS TO BE INSTALLED | | | FOR THIS PROJECT, DEPENDING OF SUB-SYSTEM SOME MAY | | | REQUIRE A IGNITION BARRIER AND OR THEERMAL BARRIER. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|