| Plan Review Notes For Permit 13090610 |
| Permit Number |
13090610 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-10-16 07:43:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2010 | | | | | | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, | | | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED | | | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE | | | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL | | | NOT BE ALTERED. | | | | | | PLEASE PROVIDE A COPY OF THE TEST REPORT. | | | | | | 2ND REVIEW, SAME DOCUMENTS SUBMITTED (ASTM 492 AND ASTM | | | E 84). PROVIDE TEST ASTM E 90. | | | | | | 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | | 109. VALUE IS TO INCLUDE LABOR AND MATERIALS, INCLUDING | | | MATERIALS SUPPLIED BY THE OWNER. | | | | | | 2ND REVIEW, CONTRACT NOT SIGNED BY OWNER AND NOT CLEAR | | | AS TO WHETHER THIS IS INSTALLATION ONLY OR IF IT | | | INCLUDES MATERIALS. | | | |
|